Precaution in lamp replacement
●
*If lamp replacement is required, please contact us.
NB: For lamp replacement, the required distance between the fitting end face and the wall surface is as follows:
■
Applicable lamp
Note: The use of a lamp other than the above lamp might result in a fire, electric shock, or explosion.
■
Reordering
When reordering, please let us know:
・
Drawing or drawing No. for the delivered product
・
Manufacturing lot number on the nameplate
1.
2. Prior to maintenance or inspection, be sure to turn off the power.
3. Confirm that the screws and bolts are fastened properly and tightly.
4. In the case of the stanchion type, be sure to provide a support at least 1500 mm above the bottom of the pole.
5.
6.
7. The supply voltage should be within the range of rating, and the supply voltage variation should be within ±6%.
8.
9. Close unused entries of the terminal box with plugs (metal).
10.
11.
12. Prior to maintenance or inspection, be sure to turn off the power.
13. To prevent shortening of the service life, avoid turning on the fitting in direct sunlight.
14. To avoid noise or malfunctioning, don't use a radio, television or wireless infrared remote control near the fitting.
15.
16.
17. The cable gland must be a product specified by SEIWA.
18.
19.
If the above information is unavailable, give us any material showing the
appearance of the product or details of the product specification
(dimensions, mounting interval, lamp type, etc.).
Distance between fitting and wall
1.2m
Model
Wattage
Lamp
Model
LLPA1WG13K3003
□
3,000K
LZAB-V2
26W
For use in an unfavorable location (a very hot, cold or humid place or a place in which there is strong wind or vibration, a salt damage
environment or a dusty or corrosive gas atmosphere), a special countermeasure should be taken.
The product must be mounted on a sturdy wall surface or structure which is vibration-free and less susceptible to damage. Otherwise, it
might fall or be damaged.
The fastening bolts on the control unit chamber housing the control unit have a tensile strength level of A20-70. Don ’ t remove the
fastening bolts. Removal of the bolts might cause a fire, electric shock or explosion.
The product should be installed at an angle within the range from 0° (oriented downward) to 90° (oriented horizontally).
Don’t install the product with its longitudinal side oriented vertically. Doing so might cause an insulation failure or electric shock.
Maintenance
Any lamp other than the applicable lamp specified below may not be used with this product. The specified lamp is not sold for any
purpose other than maintenance of the product.
The specified lamp is not sold for any purpose other than maintenance of the product. If lamp replacement is required, please contact us.
The use of a lamp other than the specified lamp might result in a fire, electric shock, or explosion. Don
’
t open the lamp house for five
minutes after turning off the power. If you don
’
t allow five minutes before opening it, an explosion might occur.
LZAB-V2
The ambient temperature should be within the range of -20°Cto +40°C. The use of the product out of this range may shorten the service
life.
In grounding work, be sure to follow the technical standards for electrical equipment and explosion-protected equipment of your country.
Inadequate grounding might cause an explosion, fire or electric shock.
Color Temperature
For outdoor use, waterproof the screwed portion of the conduit, the cable entry fittings and the joint with the stand pole to prevent
rainwater infiltration.
When installing the fitting, be sure to connect external wires inside a specified part of the fitting. Don't open any other part of the fitting
unless necessary.
The product must be used in a location where it can be used safely according to its explosion protection type (indicated on the body).
LLPA1WG13K5003
□
5,000K
CAUTIONS
Nameplate
- 3 -