background image

Precaution in lamp replacement

*If lamp replacement is required, please contact us.

NB:  For lamp replacement, the required distance between the fitting end face and the wall surface is as follows:

Applicable lamp

Note:  The use of a lamp other than the above lamp might result in a fire, electric shock, or explosion.

Reordering

When reordering, please let us know:

Drawing or drawing No. for the delivered product

Manufacturing lot number on the nameplate

1.

2. Prior to maintenance or inspection, be sure to turn off the power. 
3. Confirm that the screws and bolts are fastened properly and tightly.
4. In the case of the stanchion type, be sure to provide a support at least 1500 mm above the bottom of the pole.
5.

6.

7. The supply voltage should be within the range of rating, and the supply voltage variation should be within ±6%.
8.
9. Close unused entries of the terminal box with plugs (metal).

10.

11.

12. Prior to maintenance or inspection, be sure to turn off the power.
13. To prevent shortening of the service life, avoid turning on the fitting in direct sunlight.
14. To avoid noise or malfunctioning, don't use a radio, television or wireless infrared remote control near the fitting.
15.

16.

17. The cable gland must be a product specified by SEIWA.
18.

19.

If the above information is unavailable, give us any material showing the
appearance of the product or details of the product specification
(dimensions, mounting interval, lamp type, etc.).

Distance between fitting and wall

1.2m

Model

Wattage

Lamp

Model

LLPA1WG13K3003

3,000K

LZAB-V2

26W

For use in an unfavorable location (a very hot, cold or humid place or a place in which there is strong wind or vibration, a salt damage
environment or a dusty or corrosive gas atmosphere), a special countermeasure should be taken.

The product must be mounted on a sturdy wall surface or structure which is vibration-free and less susceptible to damage. Otherwise, it
might fall or be damaged.

The fastening bolts on the control unit chamber housing the control unit have a tensile strength level of A20-70. Don ’ t remove the
fastening bolts. Removal of the bolts might cause a fire, electric shock or explosion.

The product should be installed at an angle within the range from 0° (oriented downward) to 90° (oriented horizontally).
Don’t install the product with its longitudinal side oriented vertically. Doing so might cause an insulation failure or electric shock.

Maintenance

Any lamp other than the applicable lamp specified below may not be used with this product. The specified lamp is not sold for any
purpose other than maintenance of the product.

The specified lamp is not sold for any purpose other than maintenance of the product. If lamp replacement is required, please contact us.
The use of a lamp other than the specified lamp might result in a fire, electric shock, or explosion. Don

t open the lamp house for five

minutes after turning off the power. If you don

t allow five minutes before opening it, an explosion might occur.

LZAB-V2

The ambient temperature should be within the range of -20°Cto +40°C. The use of the product out of this range may shorten the service
life.
In grounding work, be sure to follow the technical standards for electrical equipment and explosion-protected equipment of your country.
Inadequate grounding might cause an explosion, fire or electric shock.

Color Temperature

For outdoor use, waterproof the screwed portion of the conduit, the cable entry fittings and the joint with the stand pole to prevent
rainwater infiltration.
When installing the fitting, be sure to connect external wires inside a specified part of the fitting. Don't open any other part of the fitting
unless necessary.

The product must be used in a location where it can be used safely according to its explosion protection type (indicated on the body).

LLPA1WG13K5003

5,000K

CAUTIONS

Nameplate

- 3 -

Summary of Contents for LZAB-V2

Page 1: ...ion pipe A and screw in the terminal box cover Confirm that the O ring is in the groove of the terminal box cover 4 Raise the fitting and fit it to the suspension hardware Hook the suspension hook onto the terminal box Explosion proof type LED Lighting Fittings LZAB V2 Performance IP rating Hazardous Area Usable in Zone 1 or Zone 2 hazardous areas where there are hydrogen gases Type of Protection ...

Page 2: ...ach other Loosen the reflector fixing screw and open the lamp house gently until it is supported by the chain The lamp house can be opened down to 90 degrees by removing the chain snap from the chain retainer Lead the applicable cable into the fitting through the cable gland and connect the power cable The white and red wires are power wires and the black wire is a grounding wire Pass the lead wir...

Page 3: ...structure which is vibration free and less susceptible to damage Otherwise it might fall or be damaged The fastening bolts on the control unit chamber housing the control unit have a tensile strength level of A20 70 Don t remove the fastening bolts Removal of the bolts might cause a fire electric shock or explosion The product should be installed at an angle within the range from 0 oriented downwa...

Page 4: ...e sure to ground For electrical connections use crimp type terminals etc to secure the connections and conduct insulation treatment An inadequate connection or inadequate insulation might cause an imperfect contact leading to an explosion fire or electric shock Be sure to turn off the power In grounding work be sure to follow the technical standards for electrical equipment and explosion protected...

Page 5: ...abnormality immediately turn off the power switch Confirm that the abnormal condition has been eliminated and make a repair call Please note that the above addresses and phone numbers may be changed CAUTION 2 19 6 Yanagibashi Taito ku Tokyo 111 0052 Japan 81 3 5833 8971 For a product marked with a frequency don t use the product at a frequency other than 50 or 60 Hz local power supply frequency Us...