4
(1) In cleaning the fitting, gently wipe with water or mild detergent. Don’t use thinner, benzene or alkaline detergent.
Such chemicals might cause discoloration or deterioration in quality and strength, resulting in a damage.
(2) Prior to maintenance, be sure to turn off the power.
(3) Conduct inspection properly referring to the table below.
(4) If a repair is needed, consult us.
Maintenance
Tighten the bolts until the seal washer is flat.
(Recommended torque value: 4.2 Nm)
(5) Adjust the angle of the fitting using the mounting
bracket.
※
The product is mounted on a ceiling. The lamp
house is installed within an angle range from 0 to
70 degrees in the left and right directions. For
angle adjustment, loosen the two hexagon socket
head bolts on the retainer. After adjustment, be
sure to tighten the hexagon socket head bolts.
(6) According to the left figure, it should be grounded
the external ground reliably.
※
The external earthing conductor should be
mounted and secured at other wires to prevent
the twisting
Grounding sign
Cross recessed pan head screw
M4
×
8 (SUS304)
(screw+spring plain washer)
Crimping terminal
R5.5-4 (Oxygen-free copper
(Tin-plated))
Tooth lock washer
M4 (SUS304)
Hexagon socket head bolt
M6
×
14 (SUS304)
Seal washer