0000137242 Rev.5.1
8
3.0
SETTINGS AND FUNCTIONALITY
3.1
INSTRUMENT DISPLAY
A
B
The right/left keys can be used to select display modes A and B
Note:
Any unavailable chemical measurements will not be displayed.
Mode A
Line 1
= Time; system water flow status
Line 2
= pH measurement display; Temperature measurement display.
Line 3
= Chlorine display; Network connection through RS485 serial port (
symbol)
Line 4
= ORP (Redox) display; Hold signal or OFA alarm flashing display, Available Alarms list display.
Mode B
Line 1
= pH dosing pump status, pH measurement display, Hold signal or OFA alarm flashing display.
Line 2
= Chlorine dosing pump status, Chlorine measurement display
Line 3
= ORP (Redox) dosing pump status, ORP (Redox) measurement display
Line 4
= Temperature relay status,Temperature measurement display; Available Alarms list display.
3.2
INSTRUMENT KEYBOARD
Esc/Mode
= Dual function key
Esc
= Exits the menu
Mode
= Displays the measurement SetPoints (hold down for 3 seconds)
Cal
= Accesses the calibration menu (hold down for 3 seconds)
Enter
= Confirms the function, Displays the alarms list (hold down for 3 seconds)
Esc+Enter =
Key
combination for accessing the programming menu (hold down for 3 seconds)
Navigation keys=
Up, Down, Right, Left for selecting parameters and navigating the menus
12:30 FLOW ON
pH 7.20 pH Tm 25.0°C
CL 1.50 ppm
ORP 750 mV Hold A
P ON pH 7.40 pH Hold
P ON CL 0.80 ppm
P OFF ORP 700 mV
R ON T 25.0°C A
Summary of Contents for Kontrol 800