0000137242 Rev.5.1
17
4.3.1 pH MEASUREMENT SETTINGS MENU (menu navigation index = 3A)
Use the
UP
and
DOWN
keys to scroll through the various menus and submenus and to modify the data
(increase/decrease).
Use the
ENTER
key to access the data insertion submenus and to confirm any modifications.
The various items contained within the pH measurement sub-menus are described below:
•
Menu index “3A1” PH RELAY
The various items contained within the pH relay’s sub-menus are described below, with their various modes,
ranges and settings:
Item
Default Value
Range
Note
On/Off
SetPoint:
7.20 pH
0-14 pH
Dose Type:
Acid
Acid / Alka
Hysteresis:
Off
0.10-3 pH
Hysteresis Time:
Off
1-900 Seconds
Start Delay:
Off
3-900 Seconds
Stop Delay:
Off
3-900 Seconds
Timed
SetPoint:
7.20 pH
0-14 pH
Dose Type:
Acid
Acid / Alka
Hysteresis:
Off
0.10-3 pH
Hysteresis Time:
Off
1-900 Seconds
Start Delay:
Off
3-900 Seconds
Stop Delay:
Off
3-900 Seconds
On Time:
1
1-1800 Sec
Off Time:
1
1-1800 Sec
PWM (Proportional)
SetPoint:
7.20 pH
0-14 pH
Dose Type:
Acid
Acid / Alka
Hysteresis:
Off
0.10-3 pH
Hysteresis Time:
Off
1-900 Seconds
Start Delay:
Off
3-900 Seconds
Stop Delay:
Off
3-900 Seconds
Period:
20 seconds
20-1800
Proportional Band:
0.3 pH
0.3-3pH
3A PH DOSING
3A1 RELAY ON/OFF
3A2 FMW (Frequency Output)
3A3 OUTmA (Current Output)
↓
3A PH DOSING
3A2 FWM (Frequency Output)
↑
3A3 OUTmA (Current Output)
3A4 ALARMS
3A1 PH RELAY
>ON/OFF
TIMED (Timed dosing)
PWM (Proportional dosing)
The pH relay’s settings can be varied as follows:
•
ON/OFF (SetPoint threshold dosing)
•
TIMED (Timed dosing)
•
PWM (Proportional dosing)