4.3.3 REDOX MEASUREMENT SETTINGS MENU (menu index 3C)
“This menu is available on the pH–Chlorine and pH–Chlorine–Redox System version”
Use the
UP
and
DOWN
keys to scroll through the various menus and submenus and to modify the data
(increase/decrease).
Use the
ENTER
key to access the data insertion submenus and to confirm any modifications.
The various items contained within the Redox measurement sub-menus are described below:
•
Menu index “3C1” REDOX RELAY
The various items contained within the pH relay’s sub-menus are described below, with their various modes,
ranges and settings:
Item
Default Value
Range
On/Off
:
SetPoint:
700 mV
±2000 mV
Dose Type:
Low
High / Low
Hysteresis:
Off
10-600 mV
Hysteresis Time:
Off
1-900 Seconds
Start Delay:
Off
3-900 Seconds
End Delay:
Off
3-900 Seconds
Timed
SetPoint:
700 mV
±2000 mV
Dose Type:
Low
High / Low
Hysteresis:
Off
10-600 mV
Hysteresis Time:
Off
1-900 Seconds
Start Delay:
Off
3-900 Seconds
End Delay:
Off
3-900 Seconds
On Time:
1
1-1800 Sec
Off Time:
1
1-1800 Sec
Proportional (PWM)
SetPoint:
700 mV
±2000 mV
Dose Type:
Low
High / Low
Hysteresis:
Off
10-600 mV
Hysteresis Time:
Off
1-900 Seconds
Start Delay:
Off
3-900 Seconds
End Delay:
Off
3-900 Seconds
Period:
20 seconds
20-1800
Proportional Band:
300 mV
20-600 mV
3C REDOX DOSING
3C1 RELAY ON/OFF
3C2 FMW
3C3 OUTmA
↓
3C REDOX DOSING
3C2 FWM
↑
3C3 OUTmA
3C4 ALARMS
3C1 RELAY REDOX
>ON/OFF
TIMED
PWM
The Redox relay’s settings can be varied as follows:
•
ON/OFF (SetPoint threshold dosing)
•
TIMED (Timed dosing)
•
PWM (Proportional dosing)