0000136904
rev. 2.0
2
Instruction Setting
Functions:
•
Calibration (Press Cal Key for 3 Seconds):
o
Select the calibration routine pH or Redox by Up or Down key.
o
Standard Routine calibration pH probe is 7 and 4 buffer solution and Redox 465 mV buffer
solution
•
Set Point (Press Set Key):
o
Press Set Key and choose SetPoint and adjust value with Up or Down Key before press
Enter and confirm.
§
Sp_750mv___700_mv_
§
Sp_7.4ph____7.6_ph_
•
Press Cal and Set Key (both) for 5 Seconds and run Program Setup:
o
Program_Menu
(Press Enter to set the following Item)
§
Language_
(It’s possible to have 5 language EN, IT, SP, DE, FR)
§
Redox_Measure
•
setpoint___750_mv
(Adjust value with enter and up or down key) It’s
possible to adjust from 0 to 1000 mV value for Redox
•
sp_type___low
(Adjust value LOW or HIGH)
•
ofa_time_000_min
(Adjust value OFF or set Time)
•
alarm_band__000_rx
(Adjust value from 100 to 300 mV )
•
Type__PROP
(Adjust value between OFF, PROP or ON/OFF )
§
ph_Measure
•
setpoint____7.4ph
(Adjust value with enter and up or down key) It’s
possible to adjust from 0 to 14 pH value.
•
sp_type___acid
(Adjust value ACID or ALKA)
•
ofa_time_000_min
(Adjust value OFF or set Time)
•
alr_band__000_ph
(Adjust value from 1 pH to 3 pH)
•
Temp__25*C_
(Adjust value with enter and up or down key) pH
measure only.
•
Type__PROP
(Adjust value between OFF, PROP or ON/OFF )
§
Flow_
(Adjust value with enter and up or down key Enable or Disable)
•
It’s possible to enable(ON) or disable (OFF) signal input
§
Calibration_probe
(Adjust value with enter and up or down key)
§
Full
(pH 7 and 4, Redox 465 mV buffer solution)
§
Easy
(pH 7, Redox 465 mV buffer solution)
§
Off
(Disabled)
§
Password
(Adjust value with enter and up or down key, standard value
0000
)
•
Save and escape Program setup with ESC key
o
Exit______save
(Adjust value with up or down key and confirm with enter key)
•
Priming Pump Keep Press UP Key for 1 seconds and priming redox pump
o
priming_____700mv
•
Priming Pump Keep Press Down Key for 1 seconds and priming pH pump
o
priming_____7.2ph
•
Lock pump function
o
Press Up and Enter (both) after 5 second flash
Rx_Stop
press again to unlock
o
Press Down and Esc (both) after 5 second flash
pH_Stop
press again to unlock
•
The unit doses in proportional mode respect at Set Point (
minimum distance 25%, maximum distance 90% of
10 minutes time period dosing)
Note
: The unit in program menu to go out in automatic mode after 1 minutes of wait time, the unit doesn’t save nothing.
enter
cal
enter
cal
set
esc
set
esc
enter
cal
prog