4.89
Date Code 20100129
Instruction Manual
SEL-751A Relay
Protection and Logic Functions
Logic Settings (SET L Command)
Counter Variables
SEL
OGIC
counters are up- or down-counting elements, updated every
processing interval.
Each counter element consists of one count setting, four control inputs, two
digital outputs, and one analog output.
shows Counter 01, the first
of 32 counters available in the device.
Figure 4.48
Counter 01
Digital output SC01QD asserts when the counter is at position zero, and
Digital output SC01QU asserts when the counter reaches the programmable
count value. Use the reset input (SC01R) to force the count to zero, and the
analog output (SC
nn
) with analog comparison operators.
describes
the counter inputs and outputs, and
shows the order of precedence
of the control inputs.
Table 4.36
Counter Input/Output Description
Name
Type
Description
SC
nn
LD
Active High Input
Load counter with the preset value to assert the output
(SC
n
QU) (follows SEL
OGIC
setting).
SC
nn
PV
Input Value
This Preset Value is loaded when SC
n
LD pulsed. This
Preset Value is the number of counts before the output
(SC
n
QU) asserts (follows SEL
OGIC
setting).
SC
nn
CU
Rising-Edge Input
Count Up increments the counter (follows SEL
OGIC
setting).
SC
nn
CD
Rising-Edge Input
Count Down decrements the counter (follows SEL-
OGIC
setting).
SC
nn
R
Active High Input
Reset counter to zero (follows SEL
OGIC
setting)
SC
nn
QU
Active High Out-
put
This Q Up output asserts when the Preset Value (maxi-
mum count) is reached (SC
n
= SC
n
PV,
n
= 01 to 32).
SC
nn
QD
Active High Out-
put
This Q Down output asserts when the counter is equal
to zero (SC
n
= 0,
n
= 01 to 32).
SC
nn
Output Value
This counter output is an analog value that may be
used with analog comparison operators in a SEL
OGIC
control equation and viewed using the
COU
com-
mand.
Table 4.37
Order of Precedence of the Control Inputs
Order
Input
1
SC
nn
R
2
SC
nn
LD
3
SC
nn
CU
4
SC
nn
CD
NOTE:
These counter elements
conform to the standard counter
function block #3 in IEC 1131-3 First
Edition 1993-03 International
Standard for Programmable
controllers—Part 3: Programming
languages.
NOTE:
For device configurations that
include either current or voltage
cards, the SEL-751A tracks the
frequency. When tracking the
frequency, the processing interval
varies with the frequency.
NOTE:
If setting SCnnCD is set to NA,
the entire counter nn is disabled).
SC01PV
SC01R
SC01LD
SC01CU
SC01CD
Counter 01
SC01QU
SC01QD
SC01
SEL
OGIC
Output
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...