4.123
Date Code 20100129
Instruction Manual
SEL-751A Relay
Protection and Logic Functions
Report Settings (SET R Command)
SER Trigger Lists
To capture element state changes in the SER report, enter the Relay Word bit
into one of the four SER (SER1 through SER4) trigger equations. Each of the
four programmable trigger equations allows entry of as many as 24 Relay
Word bits separated by spaces or commas; the SER report accepts a total of 96
Relay Word bits.
shows the settings prompt and default settings for
the four SER trigger equations.
Relay Word Bit
Aliases
To simplify your review of the information displayed in the SER record, the
relay provides the Alias setting function. Using the Alias settings, you can
change the way relay elements listed in the SER settings above are displayed
in the SER report. In addition, the Alias settings allow you to change the text
displayed when a particular element is asserted and deasserted. The relay
permits up to 20 unique aliases, as defined by the Enable Alias Settings
(EALIAS) setting. Factory default alias settings are shown in
Define the enabled alias settings by entering the Relay Word bit name, a
space, the desired alias, a space, the text to display when the condition asserts,
a space, and the text to display when the condition deasserts.
ALIAS1 = PB01 FP_AUX1 PICKUP DROPOUT
for the complete list of Relay Word bits. Use as many as
15 characters to define the alias, asserted text, and deasserted text strings. You
can use capital letters (A–Z), numbers (0–9), and the underscore character (_)
within each string. Do not attempt to use a space within a string because the
relay will interpret a space as the break between two strings. If you wish to
clear a string, simply type
NA
.
Table 4.69
SER
a
Trigger Settings
a
Use up to 24 Relay Word elements separated by spaces or commas for each setting.
Setting Prompt
Setting Name := Factory Default
SER1
SER1 := IN101 IN102 51P1T 51G1T 50P1P 50N1T 51N1T PB01
PB02 PB03 PB04
SER2
SER2 := CLOSE 52A CC
SER3
SER3 := 81D1T 81D2T
SER4
SER4 := SALARM
Table 4.70
Enable Alias Settings
Setting Prompt
Setting Range
Setting Name =
Factory Default
Enable ALIAS Settings (N, 1–20)
N, 1–20
EALIAS = 4
Table 4.71
SET R SER Alias Settings
Setting Prompt
Relay
Word Bit
Alias
Asserted
Text
Deasserted
Text
ALIAS1 :=
PB01
FP_AUX1
PICKUP
DROPOUT
ALIAS2 :=
PB02
FP_LOCK
PICKUP
DROPOUT
ALIAS3 :=
PB03
FP_CLOSE
PICKUP
DROPOUT
ALIAS4 :=
PB04
FP_TRIP
PICKUP
DROPOUT
ALIAS5 –ALIAS20
NA
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...