5.14
SEL-751A Relay
Instruction Manual
Date Code 20100129
Metering and Monitoring
Station DC Battery Monitor
Additional
Application
Other than alarming, the dc voltage elements can be used to disable reclosing.
For example, if the station dc batteries have a problem and the station dc
battery voltage is declining, drive the reclosing relay to lockout:
79DTL =
NOT(SVnT) OR....
Timer output SV
n
T is from the bottom of
. When dc voltage falls
below pickup DCHIP, timer output SV
n
T drops out (= logical 0), driving the
relay to lockout:
79DTL =
NOT(SVnT) OR ... = NOT(logical 0) OR ... = logical OR
Circuit breaker tripping and closing requires station dc battery energy. If the
station dc batteries are having a problem and the station dc battery voltage is
declining, the relay should not reclose after a trip—there might not be enough
dc battery energy to trip a second time after a reclose.
View Station DC
Battery Voltage
Via Serial Port
The
METER
command displays the station dc battery voltage (labeled VDC).
Via Front Panel
The information available via the previously discussed
METER
serial port
command is also available via the front-panel Meter Menu. See
Analyze Station DC
Battery Voltage
The station dc battery voltage is displayed in column Vdc in the example
event report in
. Changes in station dc battery voltage for an event
(e.g., circuit breaker tripping) can be observed. Use the
EVE
command to
retrieve event reports as discussed in
Station DC Battery Voltage Dips During Circuit Breaker Tripping
Event reports are automatically generated when the TRIP Relay Word bit
asserts (TRIP is the logic output of
). For example, output contact
OUT103 is set to trip:
OUT103 =
TRIP
Anytime output contact OUT103 closes and energizes the circuit breaker trip
coil, any dip in station dc battery voltage can be observed in column Vdc in
the event report.
To generate an event report for external trips, program an optoisolated input
IN
xyz
(monitoring the trip bus) in the SEL
OGIC
control equation event report
generation setting:
ER =
R_TRIG(INxyz) OR…
Anytime the trip bus is energized, any dip in station dc battery voltage can be
observed in column Vdc in the event report.
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...