5.15
Date Code 20100129
Instruction Manual
SEL-751A Relay
Metering and Monitoring
Breaker Monitor
Station DC Battery Voltage Dips During Circuit Breaker Closing
To generate an event report when the SEL-751A closes the circuit breaker,
make the SEL
OGIC
control equation event report generation setting:
ER =
R_TRIG(OUT102) OR…
In this example, output contact OUT102 is set to close:
OUT102 =
CLOSE
)
Anytime output contact
OUT102
closes and energizes the circuit breaker close
coil, any dip in station dc battery voltage can be observed in column Vdc in
the event report.
This event report generation setting (ER = R_TRIG(OUT102) OR....) might
be made just as a testing setting. Generate several event reports when doing
circuit breaker close testing and observe the “signature” of the station dc
battery voltage in column Vdc in the event reports.
Station DC Battery Voltage Dips Anytime
To generate an event report anytime there is a station dc battery voltage dip,
set the dc voltage element directly in the SEL
OGIC
control equation event
report generation setting:
ER =
F_TRIG(SVnT) OR...
Timer output SV
n
T is an example dc voltage element from the bottom of
. Anytime dc voltage falls below pickup DCHIP, timer output
SV4T drops out (logical 1 to logical 0 transition), creating a falling-edge
condition that generates an event report. Also, the Sequential Event Recorder
(SER) report can be used to time-tag station dc battery voltage dips.
Breaker Monitor
The breaker monitor in the SEL-751A helps in scheduling circuit breaker
maintenance. The breaker monitor is enabled with the enable setting:
EBMON =
Y
The breaker monitor settings in
are available via the
SET G
commands (see
). Also refer to
and
BRE n Command (Preload/Reset Breaker Wear) on
The breaker monitor is set with breaker maintenance information provided by
circuit breaker manufacturers. This breaker maintenance information lists the
number of close/open operations that are permitted for a given current
interruption level. The following is an example of breaker maintenance
information for a 25 kV circuit breaker. The breaker maintenance information
in
is plotted in
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...