9.12
SEL-751A Relay
Instruction Manual
Date Code 20100129
Analyzing Events
Event Reporting
E25 := N
55LGTP := OFF 55LDTP := OFF 55LGAP := OFF 55LDAP := OFF
81D1TP := OFF 81D2TP := OFF
81D3TP := OFF
81D4TP := OFF
TDURD := 0.5 CFD := 1.0
TR := ORED50T OR ORED51T OR 81D1T OR 81D2T OR 81D3T OR 81D4T OR 59P1T OR 59P2T OR 55T OR REMTRIP OR SV01 OR OC OR SV04T
REMTRIP := 0
ULTRIP := NOT (51P1P OR 51G1P OR 51N1P OR 52A)
52A := 0
CL := SV03T AND LT02 OR CC
ULCL := 0
E79 := OFF
Report Settings
ESERDEL := N
SER1 := IN101 IN102 51P1T 51G1T 50P1P 50N1T 51N1T PB01 PB02 PB03 PB04
SER2 := CLOSE 52A CC
SER3 := 81D1T 81D2T
SER4 := SALARM
EALIAS := 4
ALIAS1 :=PB01 FP_AUX1 PICKUP DROPOUT
ALIAS2 :=PB02 FP_LOCK PICKUP DROPOUT
ALIAS3 :=PB03 FP_CLOSE PICKUP DROPOUT
ALIAS4 :=PB04 FP_TRIP PICKUP DROPOUT
ER := R_TRIG 51P1P OR R_TRIG 51G1P OR R_TRIG 50P1P OR R_TRIG 50G1P OR R_TRIG 51N1P OR R_TRIG CF
LER := 15 PRE := 5
LDLIST := NA
LDAR := 15
Logic Settings
ELAT := 4 ESV := 5 ESC := N EMV := N
SET01 := NA
RST01 := NA
SET02 := R_TRIG SV02T AND NOT LT02
RST02 := R_TRIG SV02T AND LT02
SET03 := PB03_PUL AND LT02 AND NOT 52A
RST03 := (PB03_PUL OR PB04_PUL OR SV03T) AND LT03
SET04 := PB04_PUL AND 52A
RST04 := (PB03_PUL OR PB04_PUL OR SV04T) AND LT04
SV01PU := 0.00 SV01DO := 0.00
SV01 := WDGTRIP OR BRGTRIP OR OTHTRIP OR AMBTRIP OR (27P1T OR 27P2T) AND NOT LOP
SV02PU := 3.00 SV02DO := 0.00
SV02 := PB02
SV03PU := 0.00 SV03DO := 0.00
SV03 := LT03
SV04PU := 0.00 SV04DO := 0.00
SV04 := LT04
SV05PU := 0.25 SV05DO := 0.25
SV05 := (PB02 OR LT03 OR LT04) AND NOT SV05T
OUT101FS:= Y OUT101 := HALARM OR SALARM
OUT102FS:= N OUT102 := CLOSE
OUT103FS:= N OUT103 := TRIP
OUT301FS:= N OUT301 := 0
OUT302FS:= N OUT302 := 0
OUT303FS:= N OUT303 := 0
OUT304FS:= N OUT304 := 0
OUT401FS:= N OUT401 := 0
OUT402FS:= N OUT402 := 0
OUT403FS:= N OUT403 := 0
OUT404FS:= N OUT404 := 0
=>>
Figure 9.3
Example Standard 15-Cycle Event Report 1/4-Cycle Resolution
look in detail at one cycle of A-phase current
.
shows how the event report
ac current column data relate to the actual sampled waveform and rms values.
shows how the event report current column data can be converted
to phasor rms values. Voltages are processed similarly.
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...