D.11
Date Code 20100129
Instruction Manual
SEL-751A Relay
DNP3 Communications
DNP3 in the SEL-751A
DNP3 Settings
The DNP3 port configuration settings available on the SEL-751A are shown
in
. You can enable DNP3 on Ethernet Port 1 or on any of the serial
Ports 2 through 4, up to a maximum of three concurrent DNP3 sessions. Each
session defines the characteristics of the connected DNP3 Master, to which
you assign one of the three available custom maps. Some settings only apply
to DNP3 LAN/WAN, and are visible only when configuring the Ethernet Port.
For example, you only have the ability to define multiple sessions on port 1,
the ethernet port. Likewise, settings applicable to serial DNP3 are visible only
when configuring a serial port.
Table D.7
Port DNP3 Protocol Settings
(Sheet 1 of 2)
Name
Description
Range
Default
EDNP
a
Enable DNP3 Sessions
0–3
0
DNPNUM
DNP3 TCP and UDP Port
1–65534
20000
DNPADR
Device DNP3 address
0–65534
0
Session 1 Settings
DNPIP1
IP address (zzz.yyy.xxx.www)
15 characters
“”
DNPTR1
Transport protocol
UDP, TCP
TCP
DNPUDP1
UDP response port
REQ, 1–65534
20000
REPADR1
DNP3 address of the Master to send messages to
0–65519
1
DNPMAP1
DNP3 Session Custom Map
1–3
1
DVARAI1
Analog Input Default Variation
1–6
4
ECLASSB1
Class for binary event data, 0 disables
0–3
1
ECLASSC1
Class for counter event data, 0 disables
0–3
0
ECLASSA1
Class for analog event data, 0 disables
0–3
2
DECPLA1
Decimal places scaling for Current data
0–3
1
DECPLV1
Decimal places scaling for Voltage data
0–3
1
DECPLM1
Decimal places scaling for Miscellaneous data
0–3
1
ANADBA1
Analog reporting dead band for current; hidden if ECLASSA1 set to 0
0–32767
100
ANADBV1
Analog reporting dead band for voltages; hidden if ECLASSA1 set to 0
0–32767
100
ANADBM1
Analog reporting dead band for miscellaneous analogs; hidden if ECLASSA and
ECLASSC set to 0
0–32767
100
TIMERQ1
Time-set request interval, minutes (M = Disables time sync requests, but still accepts
and applies time syncs from Master; I = Ignores (does not apply) time syncs from
Master)
I, M, 1–32767
I
STIMEO1
Select/operate time-out, seconds
0.0–30.0
1.0
DNPINA1
Send Data Link Heartbeat, seconds; hidden if DNPTR1 set to UDP
0.0–7200
120
DRETRY1
b
Data link retries
0–15
3
DTIMEO1
Data link time-out, seconds; hidden if DRETRY1 set to 0
0.0–5.0
1
ETIMEO1
Event message confirm time-out, seconds
1–50
5
UNSOL1
Enable unsolicited reporting; hidden and set to N if ECLASSB1, ECLASSC1, and
ECLASSA1 set to 0
Y, N
N
PUNSOL1
Enable unsolicited reporting at power up; hidden and set to N if UNSOL1 set to N
Y, N
N
NUMEVE1
c
Number of events to transmit on
1–200
10
AGEEVE1
Oldest event to transmit on, seconds
0.0–99999.0
2.0
URETRY1
Unsolicited messages maximum retry attempts
2–10
3
UTIMEO1
Unsolicited messages offline timeout, seconds
1–5000
60
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...