2.17
Date Code 20100129
Instruction Manual
SEL-751A Relay
Installation
Rear-Panel Connections
Figure 2.12
Fiber-Optic Serial, Ethernet, EIA-232 Communication, 4 DO/3 DI/1AO, and 3 AVI/4 AFDI Voltage
Option With Arc-Flash Detector Inputs
Power Connections
The
POWER
terminals on the rear panel (
A01(+/H)
and
A02(—/N)
) must connect to
110–240 Vac, 110–250 Vdc, or 24–48 Vdc (see
for complete power input specifications). The
POWER
terminals are isolated
from chassis ground. Use 14 AWG (2.5 mm
2
) to 16 AWG (1.5 mm
2
) size wire
to connect to the
POWER
terminals.
Place an external circuit breaker or switch no more than 3.0 m (9.8 feet) from
the equipment. The circuit breaker (or equivalent approved disconnect device
appropriate for the country of installation) must comply with IEC 60947-1 and
IEC 60947-3 and be identified as the disconnect device for the equipment and
be located near the equipment. This disconnect device must interrupt both the
hot
(H)
and the neutral
(N)
power leads.
The maximum current rating for the power disconnect circuit breaker or
overcurrent device (fuse) must be 20 A. An internal power supply fuse
(T 3.15 A H250 V 5 x 20 mm) protects the operational power supply. Be sure
to use fuses that comply with IEC 60127-2.
Grounding (Earthing)
Connections
You must connect the ground terminal labeled
GND
on the rear panel to a rack
frame or switchgear ground for proper safety and performance. Use 14 AWG
(2.5 mm
2
) wire less than 2 m (6.6 feet) in length for the ground connection.
Serial Ports
Because all ports (
F
,
2
,
3
, and
4
) are independent, you can communicate to any
combination simultaneously. Although serial
Port 4
on the optional
communications card consists of an EIA-485 (
4A
) and an EIA-232 (
4C
) port,
only one port is available at a time. Use the
Port 4
communications interface
COMMINF setting to select between EIA-485 and EIA-232.
i4317a
i4318a
(A) Rear-Panel Layout
(B) Side-Panel Input and Output Designations
Contact with instrument terminals
can cause electrical shock that can
result in injury or death.
!
DANGER
The relay contains devices sensitive
to Electrostatic Discharge (ESD).
When working on the relay with the
front panel removed, work surfaces
and personnel must be properly
grounded or equipment damage may
result.
!
CAUTION
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...