H.5
Date Code 20100129
Instruction Manual
SEL-751A Relay
Synchrophasors
Settings for Synchrophasors
PROTO := PMU Does Not Allow Commands on That Serial Port
The PROTO := PMU settings choice in
can be made even when
Global setting EPMU := N. However, in this situation, the serial port will not
respond to any commands or requests. Either enable synchrophasors by
making the
settings, or change the port PROTO setting to SEL.
If you use a computer terminal session or
AC
SEL
ERATOR
QuickSet
®
SEL-5030
®
software connected to a serial port, and then set that same serial
port PROTO setting to PMU, you will lose the ability to communicate with the
relay through ASCII commands or virtual file interface commands. If this
happens, either connect via another serial port (that has PROTO := SEL) or
use the front-panel HMI SET/SHOW screen to change the disabled port
PROTO setting back to SEL.
Descriptions of Synchrophasor Settings
Definitions for the settings in
are as follows:
MRATE
Selects the message rate in messages per second for synchrophasor data
streaming on serial ports.
Choose the MRATE setting that suits the needs of your PMU application. This
setting is one of six settings that determine the minimum port SPEED
necessary to support the synchrophasor data packet rate and size. See
Communications Bandwidth on page H.10
for detailed information.
PMSTN and PMID
Defines the name and number of the PMU.
The PMSTN setting is an ASCII string with as many as 16 characters. The
PMID setting is a numeric value. Use your utility or synchrophasor data
concentrator naming convention to determine these settings.
PHDATAV and VCOMP
PHDATAV selects which voltage synchrophasors to include in the data packet.
Consider the burden on your synchrophasor processor and offline storage
requirements when deciding how much data to transmit. This setting is one of
Table H.2
SEL-751A
Serial Port Settings for Synchrophasors
Setting
Description
Default
PROTO
Protocol (SEL, MOD, EVMSG, PMU,
MBA, MBB, MB8A, MB8B, MBTA,
MBTB)
a,
b
a
Some of the other PROTO setting choices may not be available.
b
Setting choice PMU is not available on PORT 1.
SEL
c
c
Set PROTO := PMU to enable (on this port) the synchrophasor protocol.
SPEED
Data Speed (300, 1200, 2400, 4800, 9600,
19200, 38400 bps)
9600
STOPBIT
Stop Bits (1, 2)
1
RTSCTS
HDWR HANDSHAKING (Y, N)
N
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...