H.10
SEL-751A Relay
Instruction Manual
Date Code 20100129
Synchrophasors
C37.118 Synchrophasor Protocol
=>
MET PM <Enter>
SEL-751A Date: 10/24/2008 Time: 02:43:44
FEEDER RELAY Time Source: External
Time Quality Maximum time synchronization error: 0.000 (ms) TSOK = 0
Synchrophasors
Phase Voltages Sync Voltage Pos. Seq. Voltage
VA VB VC VS V1
MAG (V) 134.14 131.64 128.60 120.79 131.45
ANG (DEG) 129.22 10.57 -111.89 129.50 129.50
Phase Currents Neut. Current Pos. Seq. Current
IA IB IC IN I1
MAG (A) 365.40 359.22 379.54 12.00 367.91
ANG (DEG) 114.78 -2.35 -120.40 -26.35 118.65
FREQ (Hz) 60.000
Rate-of-change of FREQ (Hz/s) 0.00
Digitals
SV24 SV23 SV22 SV21 SV20 SV19 SV18 SV17
0 0 1 0 0 0 1 0
SV32 SV31 SV30 SV29 SV28 SV27 SV26 SV25
1 0 0 0 1 0 0 0
Analogs
MV29 2.123 MV30 10.450 MV31 -120.300 MV32 40.120
=>
Figure H.4
Sample MET PM Command Response
C37.118 Synchrophasor Protocol
The SEL-751A complies with IEEE C37.118, Standard for Synchrophasors
for Power Systems. The protocol is available on serial ports 2, 3, 4, and F by
setting the corresponding Port setting PROTO := PMU.
This subsection does not cover the details of the protocol, but highlights some
of the important features and options that are available.
Settings Affect
Message Contents
The SEL-751A allows several options for transmitting synchrophasor data.
These are controlled by Global settings described in
. You can select how often to transmit the
synchrophasor messages (MRATE) and which synchrophasors to transmit
(PHDATAV and PHDATAI). The SEL-751A automatically includes the
frequency and rate-of-change of frequency in the synchrophasor messages.
The relay can include up to four user-programmable analog values in the
synchrophasor message, as controlled by Global setting NUMANA, and 0 or
16 digital status values, as controlled by Global setting NUMDSW.
The SEL-751A always includes the results of four synchrophasor trigger
reason SEL
OGIC
equations TREA1, TREA2, TREA3, and TREA4, and the
trigger SEL
OGIC
equation result PMTRIG, in the synchrophasor message.
Communications
Bandwidth
A phasor measurement unit (PMU) that is configured to transmit a single
synchrophasor (positive-sequence voltage, for example) at a message rate of
once per second places little burden on the communications channel. As more
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...