4.48
SEL-751A Relay
Instruction Manual
Date Code 20100129
Protection and Logic Functions
Rate-of-Change of Frequency Protection
NOTE:
The relay measures system
frequency for these elements with the
positive-sequence voltage if the
voltage input option is present and
the applied positive-sequence voltage
is greater than 10 volts for at least
three cycles. Otherwise, the relay uses
positive-sequence current.
The SEL-751A provides six trip over- or underfrequency elements with
independent level and time-delay settings. When an element level setting is
less than the nominal frequency setting, the element operates as an
underfrequency element. When the level setting is greater than the nominal
frequency setting, the element operates as an overfrequency element.
shows the logic diagram for the frequency elements.
Figure 4.27
Over- and Underfrequency Element Logic
Rate-of-Change of Frequency Protection
Frequency changes occur in power systems when there is an unbalance
between load and active power generated. Typically, generator control action
adjusts the generated active power and restores the frequency to nominal
value. Failure of such control action may lead to system instability unless
remedial action, such as load shedding, is taken. You can use the rate of
change of frequency element to detect and initiate a remedial action. The
SEL-751A provides four rate-of-change of frequency elements.
shows settings available for the elements.
freq
81DnTP
81DnT
81DnTP
<
FNOM
FREQTRK
81DnTD
0
Frequency Elements 1–6
Measured Frequency
Frequency Pickup Setting
Nominal Frequency Setting
Over- and Underfrequency Element Pickup Time Delay
Definite-Time Delayed Over- and Underfrequency Element Relay Word Bit
Relay Is Tracking Frequency
n =
freq =
81DnTP =
FNOM =
81DnTD =
81DnT =
FREQTRK =
81DnTP
≥
FNOM
Table 4.23
Rate-of-Change-of-Frequency Settings
(Sheet 1 of 2)
Setting Prompt
Setting Range
Setting Name :=
Factory Default
ENABLE 81R
OFF, 1–4
E81R := OFF
81R VOLTAGE SUP
OFF, 0.1–1.3*Vnm
a
81RVSUP := 0.1*Vnm
81R CURRENT SUP
OFF, 0.1–2.0*
I
NOM
b
81RISUP := OFF
81R1 TRIP LEVEL
OFF, 0.10–15.00
81R1TP := OFF
81R1 TREND
INC, DEC, ABS
81R1TRND := ABS
81R1 TRIP DELAY
0.10–60.00 sec
81R1TD := 1.00
81R1 DO DELAY
0.00–60.00 sec
81R1DO := 0.00
81R2 TRIP LEVEL
OFF, 0.10–15.00
81R2TP := OFF
81R2 TREND
INC, DEC, ABS
81R2TRND := ABS
81R2 TRIP DELAY
0.10–60.00 sec
81R2TD := 1.00
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...