4.59
Date Code 20100129
Instruction Manual
SEL-751A Relay
Protection and Logic Functions
Reclose Logic
programmable timer before using it in the preceding 79CLS and 79STL
settings for the SEL-751A(2) (see
). Note the built-in 2-cycle
qualification of the synchronism-check voltages shown in
EXAMPLE 4.6
Settings Example 2
Refer to subsection
Synchronism-Check Elements on page 4.33
. Also
If the synchronizing voltages across open circuit breaker 52/2 are
“slipping” with respect to one another, the Reclose Supervision Limit
Timer setting 79CLSD should be set greater than zero so there is time
for the slipping voltages to come into synchronism. For example:
79CLSD :=
1.00 second
79CLS :=
25A1
The status of synchronism-check element 25A1 is checked
continuously during the 60-cycle window. If the slipping voltages
come into synchronism while timer 79CLSD is timing, synchronism-
check element 25A1 asserts to logical 1 and reclosing proceeds.
In the above referenced subsection, note item 3 under
Check Element Outputs on page 4.40
, Voltages VP and VS are
“Slipping.” Item 3 describes a last attempt for a synchronism-check
reclose before timer 79CLSD times out (or setting 79CLSD := 0.00
and only one check is made).
If E79 := 3 (which allows three automatic reclose attempts) and the
slipping voltages fail to come into synchronism while timer 79CLSD is
timing (resulting in a reclose supervision failure, causing RCSF to
assert for one processing interval), then the reclosing relay goes to
the Lockout State.
Reclose Logic
Note that input:
Reclosing Relay Open Interval Time-Out
is the logic input that is qualified by SEL
OGIC
control equation
setting 79CLS, and then propagated on to the close logic in
to
automatically reclose a circuit breaker. The explanation that follows in this
reclosing relay subsection describes all the reclosing relay settings and logic
that eventually result in this open interval time-out logic input into
. Other aspects of the reclosing relay are also explained. Up to four
(4) automatic reclosures (shots) are available.
The reclose enable setting, E79, has setting choices OFF, 1, 2, 3, and 4. Setting
E79 = OFF defeats the reclosing relay. Setting choices 1 through 4 are the
number of desired automatic reclosures (see
). Setting choices 1 through 4 also have the reclosing relay go to the
Lockout state upon reclose supervision failure (refer to
).
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...