4.63
Date Code 20100129
Instruction Manual
SEL-751A Relay
Protection and Logic Functions
Reclose Logic
Reclosing Control
Settings
The reclosing control settings are shown in
:
The operation of open interval timers is affected by SEL
OGIC
control equation
settings discussed later in this section.
Open Interval Timers
The reclose enable setting, E79, determines the number of open interval time
settings that can be set. For example, if setting E79 := 3, the first three open
interval time settings in
, are made available for setting.
If an open interval time is set to zero, then that open interval time is not
operable,
and
neither are the open interval times that follow it.
, the open interval 2 time setting 79OI2 is
the first open interval time setting set equal to zero:
79OI2 :=
0.00 seconds
Thus, open interval times 79OI2, 79OI3, and 79OI4 are not operable. In the
factory settings, both open interval times 79OI3 and 79OI4 are set to zero. But
if the settings were:
79OI2 :=
0.00 seconds
79OI3 :=
15.00 seconds
(set to some value other than zero)
open interval time 79OI3 would still be inoperative, because a preceding open
interval time is set to zero (i.e., 79OI2 := 0.00).
Table 4.27
Reclosing Control Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
ENABLE RECLOSER
OFF, 1–4 Shots
E79 := OFF
OPEN INTERVAL 1
0.00–3000.00 secs
79OI1 := 5.00
OPEN INTERVAL 2
0.00–3000.00 secs
79OI2 := 0.00
OPEN INTERVAL 3
0.00–3000.00 secs
79OI3 := 0.00
OPEN INTERVAL 4
0.00–3000.00 secs
79OI4 := 0.00
RST TM FROM RECL
0.00–3000.00 secs
79RSD := 15.00
RST TM FROM LO
0.00–3000.00 secs
79RSLD := 5.00
RECLS SUPV TIME
OFF, 0.00–3000.00 secs
79CLSD := 0.00
RECLOSE INITIATE
SV
79RI := TRIP
RCLS INIT SUPVSN
SV
79RIS := 52A OR 79CY
DRIVE-TO-LOCKOUT
SV
79DTL := OC OR SV04T
DRIVE-TO-LSTSHOT
SV
79DLS := 79LO
SKIP SHOT
SV
79SKP := 0
STALL OPN INTRVL
SV
79STL := TRIP
BLOCK RESET TMNG
SV
79BRS := TRIP
SEQ COORDINATION
SV
79SEQ := 0
RCLS SUPERVISION
SV
79CLS := 1
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...