4.83
Date Code 20100129
Instruction Manual
SEL-751A Relay
Protection and Logic Functions
Logic Settings (SET L Command)
Latch Bits:
Nonvolatile State
Power Loss
The states of the latch bits (LT01–LT32) are retained if power to the device is
lost and then restored. If a latch bit is asserted (e.g., LT02 := logical 1) when
power is lost, it is asserted (LT02 := logical 1) when power is restored. If a
latch bit is deasserted (e.g., LT03 := logical 0) when power is lost, it is
deasserted (LT03 := logical 0) when power is restored.
Settings Change
If individual settings are changed, the states of the latch bits (Relay Word bits
LT01 through LT32) are retained, as in the preceding
explanation. If the individual settings change causes a change in SEL
OGIC
control equation settings SET
n
or RST
n
(
n
= 1 through 32), the retained states
of the latch bits can be changed, subject to the newly enabled settings SET
n
or
RST
n
.
Make Latch Control Switch Settings With Care
The latch bit states are stored in nonvolatile memory so they can be retained
during power loss or settings change. The nonvolatile memory is rated for a
finite number of writes for all cumulative latch bit state changes. Exceeding
the limit can result in a flash self-test failure.
An average of 70 cumulative
latch bit state changes per day can be made for a 25-year device service life.
Settings SET
n
and RST
n
cannot result in continuous cyclical operation of
latch bit LT
n
. Use timers to qualify conditions set in settings SET
n
and RST
n
.
If you use any optoisolated inputs in settings SET
n
and RST
n
, the inputs each
have a separate debounce timer that can help in providing the necessary time
qualification.
SEL
OGIC
Control
Equation Variables/
Timers
Enable the number of SEL
OGIC
control equations necessary for your
application. Only the enabled SEL
OGIC
control equations appear for settings.
Each SEL
OGIC
control equation variable/timer has a SEL
OGIC
control
equation setting input and variable/timer outputs as shown in
.
Timers SV01T through SV32T in
have a setting range of 0.00–
3000.00 seconds. This timer setting range applies to both pickup and dropout
times (SV
n
PU and SV
n
DO,
n
= 1 through 32).
Figure 4.45
SEL
OGIC
Control Equation Variable/Timers SV01/SV01T—SV32T
You can enter up to 15 elements per SEL
OGIC
equation, including a total of 14
elements in parentheses (see
for more information).
SVn
SVn
SVnT
SEL
OGIC
Variable/
Timer Input Settings
Relay
Word
Bits
SVnPU
SVnDO
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...