Instruction Manual
SEL-751A Relay
Protection and Logic Functions
Arc-Flash Protection
Figure 4.51
Breaker Failure Logic
Arc-Flash Protection
The SEL-751A offers advanced arc-flash protection capability aimed at
minimizing the hazards associated with high energy arc (faults) in metal-
enclosed and metal-clad switchgear. The system supports four fiber-optic light
sensors capable of detecting the high energy arc-flash events and tripping the
breaker within milliseconds of the fault. Light sensors are supervised with an
instantaneous overcurrent element offering enhanced security against false
trips. Each of the four sensors can be routed to multiple tripping outputs using
SEL
OGIC
equations, offering ultimate flexibility in creating multiple
protection zones (breaker truck cabinet, bus, PT cubicle etc).
SEL-751A arc-flash protection is exceptionally fast. Typical relay operating
times are in the order of 2–5 ms when equipped with the optional fast hybrid
(high-speed) output card. With standard, electromechanical outputs, tripping
time increases to 7–13 ms. Fault clearing time will typically be longer,
determined by the breaker operating time, which often adds three to five
cycles.
This system supports two distinct types of fiber-optic light sensors. The first
type is the omni-directional
point sensor
optimized for installation in
individual switchgear compartments. The second sensor is the
bare-fiber
loop
sensor optimized for protection of long, distributed resources, such as the
switchgear bus compartment. Both types of sensors are supervised by using a
loopback-based attenuation measurement method, and can be used
interchangeably on each of the four light inputs.
Arc-Flash
Overcurrent Elements
(50PAF, 50NAF)
shows the settings for the arc-flash instantaneous overcurrent
elements. Two elements are provided; the three-phase overcurrent element
50PAF and the neutral overcurrent element 50NAF.
52ABF = Y
BFI
Setting
52A
0.02 • I
NOM
|I1| + |I2|
BFD
0
Relay
Word
Bit
BFT
Relay
Word
Bit
Table 4.43
Arc-Flash Overcurrent Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
AF PH OC TRP LVL
OFF, 0.50-100.00 A
a
a
For I
NOM
= 5 A (Phase and Neutral respectively)
50PAFP := OFF
0.10-20.00 A
b
b
For I
NOM
= 1 A (Phase and Neutral respectively)
AF N OC TRP LVL
OFF, 0.50-100.00 A
50NAFP := OFF
0.10-20.00 A
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...