6.4
SEL-751A Relay
Instruction Manual
Date Code 20100129
Settings
View/Change Settings Over Communications Port
View/Change Settings Over Communications Port
for information on how to set up and
access the relay serial or Ethernet port with a personal computer and how to
use ASCII commands to communicate with the relay.
View Settings
Use the
SHOW
command to view relay settings. The
SHOW
command is
available from Access Level 1 and Access Level 2.
lists the
SHOW
command options.
You may append a setting name to each of the commands to specify the first
setting to display (e.g.,
SHO 50P1P
displays the relay settings starting with
setting
50P1P
). The default is the first setting. The
SHOW
command displays
only the enabled settings.
Enter Settings
The
SET
command (available from Access Level 2) allows you to view or
change settings.
lists the
SET
command options.
You may append a setting name to each of the commands to specify the first
setting to display (e.g.,
SET 50P1P
displays the relay settings starting with
setting 50P1P). The default is the first setting.
Table 6.2
SHOW Command Options
Command
Description
SHOW
n
Show relay group settings:
n
specifies the settings group (1, 2, or 3);
n
defaults to active settings group if not listed.
SHO L
n
Show logic settings:
n
specifies the settings group (1, 2, or 3);
n
defaults to
active settings group if not listed.
SHO G
Show global configuration settings.
SHO P
n
Show serial port settings for port
n
(
n
= F, 1, 2, 3, or 4).
SHO F
Show front-panel display and LED settings.
SHO R
Show Sequential Event Report (SER) and Event Report settings.
SHO M
Show Modbus settings.
SHO D
Show DNP3 map settings.
Table 6.3
SET Command Options
Command
Settings Type
Description
SET
n
Relay
Protection elements, timers, etc., for settings group
n
(1, 2, or 3)
SET L
n
Logic
SEL
OGIC
control equations for settings group
n
(1, 2, or 3)
SET G
Relay
Global configuration settings including Event Messen-
ger, optoisolated input debounce timers, etc.
SET P
n
Port
Serial port settings for serial port
n
(1, 2, 3, 4, or F)
SET F
Front Panel
Front-panel display and LED settings
SET R
Reports
SER and Event Report settings
SET M
Modbus
Modbus user map
SHO D
DNP
DNP3 map settings
NOTE:
The
SET
command is not
available up to 90 seconds after the
relay is powered up and up to
40 seconds after a setting change. If
you issue a
SET
command during this
period, the relay responds with the
following message:
Command Unavailable;
Relay Configuration in
Progress, Try Again.
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...