7.19
Date Code 20100129
Instruction Manual
SEL-751A Relay
Communications
SEL ASCII Protocol and Commands
=>>AFT
Arc Flash Diagnostic in progress . . . . . . . . . . . . .
SEL-751A Date: 12/09/2008 Time: 09:20:13
FEEDER RELAY Time Source: Internal
Channel # Sensor Test Light Limits Measured Sensor Excess Ambient
Type Min(%) Max(%) Test Light(%) Diagnostic Light
AF Input 1 Fiber 20.00 100.00 31.94 Pass OK
AF Input 2 Fiber 20.00 100.00 27.08 Pass OK
AF Input 3 None ---.-- ---.-- ---.-- --- ---
AF Input 4 Point 0.10 30.00 2.27 Pass OK
=>>
Figure 7.16
AFT Command Response
ANALOG Command
Use the
ANA
command to test an analog output by temporarily assigning a
value to an analog output channel (see
for the command description
and
for the format). After entering the
ANA
command, the device
suspends normal operation of the analog output channel and scales the output
to a percentage of full scale. After assigning the specified value for the
specified time, the device returns to normal operation. Entering any character
(including pressing the space key) ends the command before reaching the
specified interval completion. You can test the analog output in one of the
following two modes:
➤
Fixed percentage: Outputs a fixed percentage of the signal for a
specified duration
➤
Ramp: Ramps the output from minimum to maximum of full
scale over the time specified
NOTE:
0% = low span, 100% = high
span. For a scaled output from 4–
20 mA, 0 percent is 4 mA and
100 percent is 20 mA.
When parameter
p
is a percentage, the relay displays the following message
during the test:
Outputting xx.xx [units] to Analog Output Port for y.y
minutes. Press any key to end test
Table 7.7
ANALOG Command
Command
Description
Access Level
ANA
c
p t
Temporarily assigns a value to an analog output
channel.
2
Table 7.8
ANALOG Command Format
Parameter
Description
c
Parameter
c
is the analog channel (either the channel name, e.g.,
A0301, or the channel number, e.g., 301).
p
Parameter
p
is a percentage of full scale, or either the letter “R” or
“r” to indicate ramp mode.
t
Parameter
t
is the duration (in decimal minutes) of the test.
where:
xx.xx
is the calculation of percent of full scale
[units]
is either mA or V, depending on the channel type setting
y.y
is the time in minutes
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...