1.20
SEL-751A Relay
Instruction Manual
Date Code 20100129
Introduction and Specifications
Specifications
Specifications
U.Instruction Manual
General
AC Current Input
Phase and Neutral Currents
I
NOM
= 1 A, 5 A, 50 mA, or 2.5 mA (high sensitivity) secondary
depending on model.
INOM = 5 A
Rated Range (X/R = 40):
0.10–100.00 A
Continuous Rating:
15 A
1 Second Thermal:
500 A
Rated Frequency:
50/60 ±5 Hz
Burden (per phase):
< 0.1 VA
INOM = 1 A
Rated Range (X/R = 40):
0.02–20.00 A
Continuous Rating:
15 A
1 Second Thermal:
100 A
Rated Frequency:
50/60 ±5 Hz
Burden (per phase):
< 0.01 VA
INOM = 50 mA
Rated Range (X/R = 40):
5.0–1000.0 mA
Continuous Rating:
15 A
1 Second Thermal:
100 A
Rated Frequency:
50/60 ±5 Hz
Burden (per phase):
< 2 mVA
INOM = 2.5 mA
Rated Range (X/R = 40):
0.13–12.50 mA
Continuous Rating:
15 A
1 Second Thermal:
100 A
Rated Frequency:
50/60 ±5 Hz
Burden (per phase):
< 0.1 mVA
Measurement Category:
II
AC Voltage Inputs
Rated Operating
100–250 Vac
Rated Continuous Voltage:
300 Vac
10 Second Thermal:
600 Vac
Rated Frequency:
50/60 ±5 Hz
Burden:
< 0.1 VA
Power Supply
High-Voltage Supply
Rated Supply Voltage:
110–240 Vac, 50/60 Hz
110–250 Vdc
Input Voltage Range:
85–264 Vac
85–275 Vdc
Power Consumption:
<40 VA (ac)
<20 W (dc)
Interruptions:
50 ms @ 125 Vac/Vdc
100 ms @ 250 Vac/Vdc
Low-Voltage Supply
Rated Supply Voltage:
24–48 Vdc
Input Voltage Range:
19.2–52.8 Vdc
Power Consumption:
<20 W (dc)
Interruptions:
10 ms @ 24 Vdc
50 ms @ 48 Vdc
Output Contacts
General
OUT103
is Form C Trip Output, all other outputs are Form A.
Dielectric Test Voltage:
2000 Vac
Impulse Withstand Voltage
(U
imp
):
4000 V
Mechanical Durability:
10,000 no load operations
Pickup/ Dropout Time:
≤
8 ms (coil energization to contact
closure)
DC Output Ratings
Rated Operational Voltage:
250 Vdc
Rated Voltage Range:
19.2–275 Vdc
Rated Insulation Voltage:
300 Vdc
Make:
30 A @ 250 Vdc per IEEE C37.90
Continuous Carry:
6 A @ 70°C
4 A @ 85°C
Thermal:
50 A for 1 s
Contact Protection:
360 Vdc, 40 J MOV protection across
open contacts
Breaking Capacity (10,000 operations) per IEC 60255-0-20:1974:
24 Vdc
.75 A
L/R = 40 ms
48 Vdc
0.50 A
L/R = 40 ms
125 Vdc
0.30 A
L/R = 40 ms
250 Vdc
0.20 A
L/R = 40 ms
Cyclic (2.5 cycles/second) per IEC 60255-0-20:1974:
24 Vdc
0.75 A
L/R = 40 ms
48 Vdc
0.50 A
L/R = 40 ms
125 Vdc
0.30 A
L/R = 40 ms
250 Vdc
0.20 A
L/R = 40 ms
AC Output Ratings
Maximum Operational
Voltage (U
e
) Rating:
240 Vac
Insulation Voltage (U
i
)
Rating (excluding
EN 61010-1):
300 Vac
Utilization Category:
AC-15 (control of electromagnetic
loads > 72 VA)
Contact Rating Designation: B300 (B = 5 A, 300 = rated insulation
voltage)
Voltage Protection Across
Open Contacts:
270 Vac, 40 J
Rated Operational
Current (I
e
):
3 A @ 120 Vac
1.5 A @ 240 Vac
Conventional Enclosed
Thermal Current (I
the
)
Rating:
5 A
Rated Frequency:
50 /60 ± 5 Hz
Electrical Durability Make
VA Rating:
3600 VA, cos
φ
= 0.3
Electrical Durability Break
VA Rating:
360 VA, cos
φ
= 0.3
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...