9.6
SEL-751A Relay
Instruction Manual
Date Code 20100129
Analyzing Events
Event Reporting
➤
Maximum feeder current
➤
Frequency
➤
Target LED status
=>>
HIS <Enter>
SEL-751A Date: 02/28/2007 Time: 15:06:13
FEEDER RELAY Time Source: Internal
FID = SEL-751A-R100-V0-Z001001-D20070410
# DATE TIME EVENT CURRENT FREQ TARGETS
1 02/28/2007 13:58:23.629 Trigger 110.7 60.0 10000000
2 02/28/2007 13:54:10.003 Phase 51 Trip 1170.1 60.0 11010001
3 02/28/2007 13:54:09.607 ER Trigger 1190.1 60.0 11010001
4 02/28/2007 13:47:36.121 Phase 51 Trip 1172.4 59.9 11010000
5 02/28/2007 13:47:35.725 ER Trigger 1171.7 59.9 10000000
6 02/28/2007 13:43:30.393 Phase 51 Trip 483.9 60.1 11010001
7 02/28/2007 13:43:29.347 ER Trigger 484.9 60.0 11010001
=>>
Figure 9.2
Sample Event History
Viewing the Event History
Access the history report from the communications ports, using the
HIS
command or the analysis menu within
AC
SEL
ERATOR
QuickSet
®
SEL-5030
software. View and download history reports from Access Level 1 and higher.
Use the
HIS
command from a terminal to obtain the event history. You can
specify the number of the most recent events that the relay returns. See
for information on the
HIS
command.
Use the front-panel
MAIN > Events > Display
menu to display event history
data on the SEL-751A front-panel display.
Use the
AC
SEL
ERATOR
QuickSet software to retrieve the relay event history.
View the
Relay Event History
dialog box via the
Tools > Events > Get
Event Files
menu.
Clearing
Use the
HIS C
command to clear or reset history data from Access Levels 1
and higher. Clear/reset history data at any communications port. This will
clear all event summaries, history records, and reports.
Event Reports
The latest event reports are stored in nonvolatile memory. Each event report
includes four sections:
➤
Analog values of current and voltage
➤
Digital states of the protection and control elements, including
overcurrent, and voltage elements, plus status of digital output
and input states
➤
Event Summary
➤
Settings in service at the time of event trigger, consisting of
Group, Logic, Global, and Report settings classes
Use the
EVE
command to retrieve the reports. There are several options to
customize the report format.
Event
Number
Event Type
Maximum
Current
User-Defined
Target LEDs
Frequency
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...