Date Code 20100129
Instruction Manual
SEL-751A Relay
SEL-751A Relay Command Summary
The table below lists the front serial port ASCII commands associated with particular activities. The commands
are shown in uppercase letters, but they can also be entered using lowercase letters.
Serial Port Command
Command Description
Access Level 0 Commands
ACC
Go to Access Level 1.
ID
Relay identification code.
QUI
Go to Access Level 0.
Access Level 1 Commands
2AC
Go to Access Level 2.
BRE
Display breaker monitor data (trips, interrupted current, wear).
CEV
n
Show compressed event report number n, at 1/4-cycle resolution. Attach R for compressed raw report, at
1/16- cycle resolution.
COM A
Return a summary report of the last 255 records in the communications buffer for M
IRRORED
B
ITS®
communications Channel A.
COM B
Return a summary report of the last 255 records in the communications buffer for M
IRRORED
B
ITS
communications Channel B.
COM C
Clears all communications records. If both M
IRRORED
B
ITS
channels are enabled, omitting
the channel specifier (A or B) clears both channels.
COM C A
Clears all communications records for Channel A.
COM C B
Clears all communications records for Channel B.
COM L
Appends a long report to the summary report of the last 255 records in the M
IRRORED
B
ITS
communications buffer.
COM L A
Appends a long report to the summary report of the last 255 records in the communications buffer for
M
IRRORED
B
ITS
communications Channel A.
COM L B
Appends a long report to the summary report of the last 255 records in the communications buffer for
M
IRRORED
B
ITS
communications Channel B.
COM S
Return a summary report of the last 255 records in the M
IRRORED
B
ITS
communications buffer.
COU
n
Show current state of device counters.
n
= repeat the report
n
times, with a 1/2 second delay between each
report.
DAT
View the date.
DAT
dd/mm/yyyy
Enter date in DMY format.
DAT
mm/dd/yyyy
Enter date in MDY format if DATE_F setting is MDY.
DAT
yyyy/mm/dd
Enter date in YMD format if DATE_F setting is YMD.
ETH
Show the Ethernet port status.
EVE
n
Show event report
n
with 4 samples per cycle. If
n
is omitted, most recent report is displayed.
EVE R
n
Show event report
n
with raw (unfiltered) 16 samples per cycle analog data and 4 samples per cycle digital
data.
FIL DIR
Return a list of files.
FIL READ
filename
Transfer settings file
filename
from the relay to the PC.
FIL SHOW
filename
Filename 1 displays contents of the file filename.
GOO
k
Display transmit and receive GOOSE messaging information. Enter number
k
to scroll the GOOSE data
k
times on the screen.
GRO
Display active group setting.
HEL
Display a short description of selected commands.
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...