2.26
SEL-751A Relay
Instruction Manual
Date Code 20100129
Installation
AC/DC Control Connection Diagrams
Voltage option is needed for voltage elements and metering (e.g., voltage, KW, KVAR). INxxx and OUTxxx indicate user-
configurable optional digital inputs and outputs.
For sensitive earth fault (SEF) applications, the SEL-751A should be ordered with Channel
IN
rated at 2.5 mA nominal.
See current input specifications in the subsection
. See neutral ground overcurrent
element pickup specifications in
Section 4: Protection and Logic Functions
.
Figure 2.22
SEL-751A Provides Overcurrent Protection for a Delta-Wye Transformer Bank (Wye-Connected PTs)
TC
Trip
Coil
52A
(+)
(—) Trip
Circuit
IA
C
B
A
SEL-751A RELAY
OUT103
CC
Close
Coil
52B
(+)
(—) Close
Circuit
IB
OUT102
86
Lock
Out
86B
(+)
(—) Breaker
Failure
Trip
Circuit
IC
OUTxxx
IN
52
(+)
52A
to Annunciator, RTU,
or SEL-2032/2030/2020
ALARM
OUT101
(+)
(—)
Breaker Status
INxxx
n
b a
c
(Low-Side)
VC
N
VB
VA
Summary of Contents for 751A
Page 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 26: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 218: ...This page intentionally left blank...
Page 250: ...This page intentionally left blank...
Page 376: ...This page intentionally left blank...
Page 392: ...This page intentionally left blank...
Page 408: ...This page intentionally left blank...
Page 418: ...This page intentionally left blank...
Page 434: ...This page intentionally left blank...
Page 462: ...This page intentionally left blank...
Page 544: ...This page intentionally left blank...
Page 580: ...This page intentionally left blank...
Page 584: ...This page intentionally left blank...
Page 632: ...This page intentionally left blank...
Page 636: ...This page intentionally left blank...
Page 640: ...This page intentionally left blank...