Schweitzer Engineering Laboratories, Inc.
SEL- 2664S Data Sheet
15
Terminal Connections for Terminal Block D
Compression Plug Tightening Torque
Minimum:
Maximum:
0.5 Nm (4.43 in-lb)
0.8 Nm (7.08 in-lb)
Compression Plug Mounting Ear Screw Tightening Torque
Minimum:
Maximum:
0.5 Nm (4.43 in-lb)
0.8 Nm (7.08 in-lb)
Wire Sizes
Use 105°C-rated wiring. Wire sizes for grounding (earthing) and power
connections are dictated by the terminal blocks and expected load
currents. Use the following table as a guide in selecting wire sizes.
Refer to
SEL Application Note AN2014-08
for wiring and termination
guidance. Strip the wires 8 mm (0.31 in) for termination and
installation.
Product Standards
Measuring Relays and Protection
Equipment:
IEC 60255-26:2013
IEC 60255-27:2013
Type Tests
Environmental Tests
Enclosure Protection:
IEC 60529:2001 + CRDG:2003
IP20 for terminals
Vibration Resistance:
IEC 60255-21-1:1998
IEC 60255-27:2013; Section 10.6.2.1
Endurance:
Class 1 (Class 2 for wall mount only)
Response:
Class 2
Shock Resistance:
IEC 60255-21-2:1998
IEC 60255-27:2013; Section 10.6.2.2
IEC 60255-27:2013; Section 10.6.2.3
Withstand:
Response:
Bump:
Class 1
Class 2
Class 1
Seismic (Quake Response):
IEC 60255-21-3:1993
IEC 60255-27:2013; Section 10.6.2.4
Response:
Class 2
Cold:
IEC 60068-2-1:2007
IEC 60255-27:2013; Section 10.6.1.2
IEC 60255-27:2013; Section 10.6.1.4
–40°C, 16 hours
Dry Heat:
IEC 60068-2-2:2007
IEC 60255-27:2013; Section 10.6.1.1
IEC 60255-27:2013; Section 10.6.1.3
85°C, 16 hours
Damp Heat, Steady State:
IEC 60068-2-78:2001
IEC 60255-27:2013; Section 10.6.1.5
40°C, 93% relative humidity, 10 days
Damp Heat, Cyclic:
IEC 60068-2-30:2001
IEC 60255-27:2013; Section 10.6.1.6
25–55°C, 6 cycles, 95% relative
humidity
Wire Size
Connection Type
a
Minimum
Maximum
Grounding (Earthing)
18 AWG (0.8 mm
2
)
14 AWG (2.1 mm
2
)
Power
16 AWG (1.3 mm
2
)
14 AWG (2.1 mm
2
)
Current (IN)
18 AWG (0.8 mm
2
)
14 AWG (2.1 mm
2
)
Potential (Voltage) (VN)
16 AWG (1.3 mm
2
)
10 AWG (5.26 mm
2
)
Contact I/O
18 AWG (0.8 mm
2
)
14 AWG (2.1 mm
2
)
a
For all connection types, the insulation voltage must be
300 V minimum.
Dielectric Strength and Impulse Tests
Dielectric (HiPot):
IEC 60255-27:2013; Section 10.6.4.3
IEEE C37.90-2005
2.5 kVac on contact outputs
3.6 kVdc on power supply IN, VN,
contact input terminals
Impulse:
IEC 60255-27:2013; Section 10.6.4.2
Severity Level: 0.5 J, 5 kV
IEEE C37.90:2005
Severity Level: 0.5 J, 5 kV
RFI and Interference Tests
EMC Immunity
Electrostatic Discharge Immunity: IEC 61000-4-2:2008
IEC 60255-26:2013; Section 7.2.3
IEEE C37.90.3:2001
Severity Level 4
8 kV contact discharge
15 kV air discharge
Radiated RF Immunity:
IEC 61000-4-3:2010
IEC 60255-26:2013; Section 7.2.4
10 V/m
IEEE C37.90.2-2004
20 V/m
Fast Transient, Burst Immunity*:
IEC 61000-4-4:2012
IEC 60255-26:2013; Section 7.2.5
4 kV @ 5.0 kHz
2 kV @ 5.0 kHz for comm. ports
Surge Immunity*:
IEC 61000-4-5:2005
IEC 60255-26:2013; Section 7.2.7
1 kV line-to-line
2 kV line-to-earth
Surge Withstand Capability
Immunity*:
IEC 61000-4-18:2010
IEC 60255-26:2013; Section 7.2.6
2.5 kV common mode
1 kV differential mode
1 kV common mode on comm. ports
IEEE C37.90.1-2002
2.5 kV oscillatory
4 kV fast transient
Conducted RF Immunity:
IEC 61000-4-6:2008
IEC 60255-26:2013; Section 7.2.8
10 Vrms
Magnetic Field Immunity:
IEC 61000-4-8:2009
IEC 60225-26:2013; Section 7.2.10
Severity Level: 1000 A/m for
3 seconds
100 A/m for 1 minute; 50/60 Hz
IEC 61000-4-9:2001
Severity Level: 1000 A/m
IEC 61000-4-10:2001
Severity Level: 100 A/m (100 kHz
and 1 MHz)
Power Supply Immunity:
IEC 61000-4-11:2004
IEC 61000-4-17:1999
IEC 61000-4-29:2000
IEC 60255-26:2013; Section 7.2.11
IEC 60255-26:2013; Section 7.2.12
IEC 60255-26:2013; Section 7.2.13
EMC Emissions
Conducted Emissions:
IEC 60255-26:2013 Class A
FCC 47 CFR Part 15.107 Class A
ICES-003 Issue 6
EN 55011:2009 + A1:2010 Class A
EN 55022:2010 + AC:2011 Class A
EN 55032:2012 + AC:2013 Class A
CISPR 11:2009 + A1:2010 Class A
CISPR 22:2008 Class A
CISPR 32:2015 Class A