Overcurrent Elements
Page 6 of 7
20120723
Hands-On Activity 3: Validate Time-Overcurrent Element
In this hands-on activity, you will validate the Winding 2 time-overcurrent element.
Validate Time-Overcurrent Test Values
The instructor will use the SEL-AMS to inject secondary quantities into the relay terminals to simulate
faults (as indicated in Table 1).
Step 1
Calculate the expected operate time using the equations from Figure 5, and record your answers in
Table 2.
Figure 5 Time-Overcurrent Operation Equations
Table 2 Simulated F1 Values for Element Pickup Test
Element Name
Calculated Operate Time
at Three Times Pickup
Test Time
Percentage Difference
51P1T
51P2T
50NN2T
Step 2
Clear the SER entries.
You can perform this task by using either the
SER C
serial port command or the
AC
SEL
ERATOR
QuickSet HMI.