U.4.23
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Basic Relay Operations
Making Simple Settings Changes
Display Points and Aliases
Syntax: Relay word bit, alias name, alias for set state, alias for clear state
1:
?
IN101,"CB1","CLOSED","OPEN"<Enter>
2:
?
IN102,"CB2","CLOSED","OPEN"<Enter>
3:
?
LIST<Enter>
1: IN101,"CB1","CLOSED","OPEN"
2: IN102,"CB2","CLOSED","OPEN"
3:
?
IN105,"5 MVA XFMR Fans”,ON,OFF<Enter>
4:
?
END<Enter>
•
•
•
Display Points and Aliases
Syntax: Relay word bit, alias name, alias for set state, alias for clear state
1: IN101,"CB1","CLOSED","OPEN"
2: IN102,"CB2","CLOSED","OPEN"
3: IN105,"5 MVA XFMR Fans","ON","OFF"
•
•
•
Save settings (Y,N) ?
Y<Enter>
Saving Settings, Please Wait...........
Settings Saved
=
>>
Figure 4.14
Using Text-Edit Mode Line Editing to Set Display Points.
This procedure proposes connecting the transformer bank fan sensor to relay
input IN105. In the
SET G
(GLOBAL) command, verify that the assertion
level (setting IN105P) and the debounce time (setting IN105D) are correct for
your fan-running sensor. To access separate input parameters, you must first
enable independent control input settings with setting EICIS. To change the
input conditioning, enter these settings:
EICIS := Y
Independent Control Input Settings (Y, N)
IN105P := 80
Input IN105 Pickup Level (15–265 Vdc)
I
N105D := 0.375
Input IN105 Debounce Time (0.00–5.00 cycles)
Use the appropriate interface hardware to connect the fan-running sensor to
IN105. Choose any relay input that conforms to your requirements. See
Control Inputs on page U.2.6 in the User’s Guide
for more information on
SEL-421 Relay control inputs.
Deleting a Display Point
This example shows how you can delete a previously used display point. In
the
SET F
command, at the Display Points and Aliases prompt, use the text-
edit mode line editing commands to set and delete the display points. This
procedure shows two previously programmed display points that indicate on
the front-panel LCD the status of Circuit Breaker 1 and Circuit Breaker 2.
Relay control inputs IN101 and IN102 are the Relay Word bits for the Circuit
Breaker 1 and Circuit Breaker 2 display points, respectively (see
Edit Mode Settings Changes on page 4.21
). You can use other inputs for your
particular application. See
Control Inputs on page U.2.6 in the User’s Guide
for more information on control inputs.
The procedure in the following steps assumes that you have successfully
established communication with the relay; see
for a step-by-step procedure. In addition, you must be
Summary of Contents for SEL-421
Page 8: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 110: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 284: ...This page intentionally left blank ...