U.4.35
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Basic Relay Operations
Examining Metering Quantities
Step 3. Set the relay to a nominal operation mode. Perform the initial
global settings relay setup of
Making Initial Global Settings:
to set the relay for 60-Hz
operation, ABC phase rotation.
Step 4. Set a basic voltage and current configuration. In the
AC
SEL
ERATOR
software Settings tree view, double-click the
Global entry of the Settings tree view to expand the Global
branch (See
). Click the I and V Source Selection
branch. You will see the Current and Voltage Source Selection
dialog box of
. Click on the down button to select 1
for ESS (Current and Voltage Source Selection).
Figure 4.26
Global Alternate Source
Selection Settings in the
AC
SEL
ERATOR
Software.
Step 5. Set PT and CT ratios. In the
AC
SEL
ERATOR
Settings tree view,
click the “+” mark next to Group 1 to expand this branch (See
). Click the plus (+) mark next to Set 1. Click Line
Configuration. You will see the Line Configuration window
similar to
. Confirm that setting CTRW is 200 (the
current transformer W-input ratio), and PTRY is 2000 (the
potential transformer Y-input ratio). Save the settings and send
the Group 1 settings if you change the settings. See
and