U.4.61
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Basic Relay Operations
Operating the Relay Inputs and Outputs
=
>>
SET M<Enter>
Breaker Monitor
Breaker Configuration
Breaker 1 Monitoring (Y,N)
EB1MON :
=
N
?
<Enter>
Breaker 2 Monitoring (Y,N)
EB2MON :
=
N
?
<Enter>
Breaker 1 Trip Type (Single Pole
=
1,Three Pole
=
3)
BK1TYP :
=
1
?
3<Enter>
Breaker 2 Trip Type (Single Pole
=
1,Three Pole
=
3)
BK2TYP :
=
1
?
3<Enter>
Breaker 1 Inputs
N/O Contact Input -BK1 (SELogic Equation)
52AA1 :
=
NA
?
IN101<Enter>
Breaker 2 Inputs
A-Phase N/O Contact Input -BK2 (SELogic Equation)
52AA2 :
=
NA
?
IN102<Enter>
Breaker Monitor
Breaker Configuration
EB1MON :
=
N EB2MON :
=
N BK1TYP :
=
3 BK2TYP :
=
3
Breaker 1 Inputs
52AA1 :
=
IN101
Breaker 2 Inputs
52AA2 :
=
IN102
Save settings (Y,N) ?
Y<Enter>
Saving Settings, Please Wait...........
Settings Saved
=
>>
Figure 4.55
Setting 52AA1: Terminal.