U.5.30
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Front-Panel Operations
Operation and Target LEDs
Operation and Target LEDs
The SEL-421 Relay gives you at-a-glance confirmation of relay conditions via
operation and target LEDs. These LEDs are located in the middle of the relay
front panel.
You can reprogram all of these indicators except the ENABLED and TRIP
LEDs to reflect other operating conditions than the factory default
programming described in this subsection. Settings T
n
_LED are SEL
OGIC
control equations that, when asserted during a relay trip event, light the
corresponding LED. Parameter
n
is a number from 1 through 16 that indicates
each LED. LED positions are described in parenthesis next to each LED in
. Program settings T
n
LEDL := Y to latch the LEDs during trip
events; when you set T
n
LEDL := N, the trip latch supervision has no effect
and the LED follows the state of the T
n
_LED SEL
OGIC
control equation. The
relay reports these targets in event reports; set the alias name listed in the
report (up to eight characters) with settings T
n
LEDA. After setting the target
LEDs, issue the
TAR R
command to reset the target LEDs. For a concise
listing of the default programming on the front-panel LEDs, see
Settings on page R.9.33 in the Reference Manual
.
Use the slide-in labels to mark the LEDs with custom names. Included on the
SEL-421/SEL-421-1 Relay Product Literature CD are Customer Label
Templates to print labels for the slide-in label carrier.
Figure 5.34
Factory Default Front-Panel Target Areas.
shows the arrangement of the operation and target LEDs region
into six areas.
The six front-panel target LED areas are the following:
➤
Operational–ENABLED, TRIP
➤
Trip Type–INST, TIME, COMM, SOTF
➤
Zone Activated–ZONE 1, ZONE 2, ZONE 3, ZONE 4
➤
Phase(s) or Ground–PHASE A, PHASE B, PHASE C,
GROUND
➤
Instantaneous and Time-Delayed Overcurrent–50, 51
➤
Recloser Status–79 RESET, 79 LOCKOUT
Operational
Phase(s)
or Ground
Instantaneous
and Time-Delayed
Overcurrent
Recloser Status
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
Trip Type
Zone
Activated