U.6.31
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Testing and Troubleshooting
Checking Relay Operation
Figure 6.26
Directional Settings:
AC
SEL
ERATOR
Software.
Step 3. Upload the new settings to the SEL-421 Relay. On the File
menu, click Send. The
AC
SEL
ERATOR
software prompts you
for the settings class you want to send to the relay, as shown in
the Group Select dialog box in
. Click the check
box for Group 1 and for Breaker Monitor. Click OK. The
AC
SEL
ERATOR
software responds with a Transfer Status dialog
. If you see no error message, the new
settings are loaded in the relay.
NOTE:
The Relay Editor dialog boxes
shown in
are for the
SEL-421 Relay. The SEL-421-1 Relay
dialog boxes are similar.
Figure 6.27
Uploading Group 1 and
Breaker Monitor Settings to the SEL-421 Relay.
Table 6.8
Negative-Sequence Directional Element Settings AUTO
Calculations
Setting
Calculation
50FP
0.12 • I
nom
50RP
0.08 • I
nom
Z2F
0.5 • Z1MAG
Z2R
Z2F + 1 / (2 • I
nom
)
a2
0.1
k2
0.2