U.4.41
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Basic Relay Operations
Reading Oscillograms, Event Reports, and SER
Step 6. Trigger an event. Click the Event Trigger box. The
AC
SEL
ERATOR
software displays a prompt in a dialog box
similar to that in
. Click Yes to trigger an event.
Figure 4.33
Event Trigger Prompt:
AC
SEL
ERATOR
Software.
Reading the
Event History
The SEL-421 Relay has two convenient methods for checking whether you
successfully captured power system data. You can view the event history data
with the
AC
SEL
ERATOR
software, or you can examine internal relay file
folders for the recorded data.
Reading the Event History:
AC
SEL
ERATOR
Software
The procedure in the following steps shows how to use the
AC
SEL
ERATOR
HMI to gather relay event history information. See
page A.3.31 in the Applications Handbook
for more information on event
history.
This example assumes that you have successfully established communication
with the relay; see
Making an EIA-232 Serial Port Connection on page 4.6
for
a step-by-step procedure. In addition, you must be familiar with relay access
levels and passwords. See
Changing the Default Passwords: Terminal on
to change the default access level passwords. You should also be
familiar with the
AC
SEL
ERATOR
software. See
Step 1. Configure the communications port. Start the
AC
SEL
ERATOR
software. On the top toolbar, open the Communication menu,
and then click Port Parameters. You will see the Port
Parameters dialog box similar to
Speed, Data Bits, Parity, and Stop Bits that match the relay
settings. Defaults are 9600, 8, N, 1, respectively. Click OK to
update the
AC
SEL
ERATOR
software communications
parameters. Confirm that the Communications Status bar at the
bottom of the
AC
SEL
ERATOR
window says “Connected.”
Step 2. Confirm that you have loaded the correct passwords in the
AC
SEL
ERATOR
software. Enter your Access Level 1 password
in the Level One Password text box, and your Access Level 2
password in the Level Two Password text box. Click the OK
button to accept changes and close the dialog box.
Step 3. View the event history report. Open the
AC
SEL
ERATOR
Analysis menu and click Read History. You will see the Relay
Event History dialog box similar to that in