Reading Oscillograms, Event Reports, and SER
the relay. The SEL-5601 Analytic Assistant is a program you can use to view
COMTRADE data. Many third-party software suppliers can provide you with
programs to display and manipulate COMTRADE files.
Retrieving High-Resolution COMTRADE Data: Terminal
The relay recorded the event triggered in
Triggering an Event on page 4.39
The procedure in the following steps shows you how to retrieve the high-
resolution raw oscillography data for this event. Perform the steps listed in
Triggering an Event on page 4.39
before executing the instructions in this
example. For this procedure, you must use a communications terminal
emulation computer program capable of file transfers (this function is not
available in the
AC
SEL
ERATOR
software). If you need help finding a terminal
emulation program, please contact the SEL factory or your local Technical
Service Center.
Step 1. Prepare to monitor the relay at Access Level 1. Using a
communications terminal, type
ACC<Enter>
. Type the Access
Level 1 password and press
<Enter>
. You will see the =>
action prompt.
Step 2. View the events file directory. Type
FILE DIR EVENTS
<Enter>
to view the contents of the SEL-421 Relay events file
directory. The relay lists file names for recently recorded events
in a manner similar to that shown in
The relay shows three high-resolution oscillography files with
the file extensions .HDR, .CFG, and .DAT for each event. This
procedure uses HR_10001 as the number of the event that you
recently triggered; use the event number corresponding to your
triggered event.
=
>>
FILE DIR EVENTS<Enter>
CHISTORY.TXT RW
HISTORY.TXT RW
C4_10001.TXT RW 03/15/2001 00:25:45.384
C8_10001.TXT RW 03/15/2001 00:25:45.384
E4_10001.TXT RW 03/15/2001 00:25:45.384
E8_10001.TXT RW 03/15/2001 00:25:45.384
HR_10001.HDR RW 03/15/2001 00:25:45.384
HR_10001.CFG RW 03/15/2001 00:25:45.384
HR_10001.DAT RW 03/15/2001 00:25:45.384
=>
>
Figure 4.36
EVENTS Folder Files.
Step 3. Prepare the relay to download the high-resolution
oscillography files. Type
FILE READ EVENTS
HR_10001.*<Enter>
to ready the relay to transfer the
HR_10001.HDR, HR_10001.CFG, and HR_10001.DAT files
to your computer.
Step 4. Download the files. Perform the steps necessary for your
terminal emulation program to receive a file. Typically, these
are the file transfer steps:
➢
Specify the destination file location in your computer
file storage system and file name.
➢
Select the transfer type as Y-Modem (if this transfer
type is not already enabled).
➢
Click on Receive.