SEL-421/SEL-421-1 Relay
Basic Relay Operations
Operating the Relay Inputs and Outputs
Figure 4.56
Accessing Global Enable Settings in the
AC
SEL
ERATOR
Software.
Step 6. Access the Control Inputs settings. In the expanded Global
Settings tree view, click on the plus (+) mark next to Control
Inputs. Click on Main Board. You will see the input window
similar to that in
Figure 4.57
Control Input Settings in the
AC
SEL
ERATOR
Software.
Step 7. Set the control input IN101 debounce time. For this example,
assume that the auxiliary contacts are slow and noisy; you must
provide a slightly longer debounce time for these contacts.
Double-click the mouse cursor (or use the Tab key) to highlight
IN101D Input101 Debounce Time. Delete the present setting
by using the Delete key. Type
0.25<Enter>
. The relay checks
the new value and enters the value in the
AC
SEL
ERATOR
database.