U.5.15
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Front-Panel Operations
Front-Panel Menus and Screens
relay front-panel display by selecting EVENTS from the MAIN MENU.
shows sample EVENT SUMMARY screens for a phase-to-phase-
to-ground fault. Use the
{Right}
and
{Left}
pushbuttons to show each of the
summary screens for the event. The horizontal scroll bar indicates that you
can view other event 10002 screens. Use the
{Up}
and
{Down}
pushbuttons to
move among the events in the summary buffer. Press
{ESC}
to return to the
MAIN MENU.
Figure 5.15
EVENT SUMMARY Screens.
BREAKER MONITOR
The SEL-421 Relay features an advanced circuit breaker monitor. Select
BREAKER MONITOR screens from the MAIN MENU to view circuit
breaker monitor alarm data on the front-panel display.
shows
sample breaker monitor display screens. The BKR n ALARM COUNTER
screen displays the number of times the circuit breaker exceeded certain alarm
thresholds (see
Circuit Breaker Monitor on page A.2.2 in the Applications
). If you have two circuit breakers and have set NUMBK := 2, the
alarm submenu in
appears first. Use the navigation pushbuttons to
choose either Circuit Breaker 1 or Circuit Breaker 2. Press
{ENT}
to view the
selected circuit breaker monitor information. An example of the Circuit
Breaker 1 ALARM COUNTER screen for a single-pole tripping circuit
breaker is shown on the right side of
Figure 5.16
BREAKER MONITOR Report Screens.
RELAY ELEMENTS
(Relay Word Bits)
You can view the RELAY ELEMENTS screen to check the state of the Relay
Word bits in the SEL-421 Relay. The relay has two unique manual-scrolling
features for viewing these elements:
➤
Accelerated navigation
➤
Search
03/15/01 GROUP 1
00:00:05.387
EVENT: BCG T
LOCATION: 48.47
FREQ: 60.00
SHOT: 1P=0 3P=1
BK1 OPEN
BK2 CLOSED
EVENT SUMMARY 10002
TARGETS:
COMM
ZONE 2
PHASE B
PHASE C
GROUND
50
EVENT SUMMARY 10002
FAULT QUANTITIES
(kV/A)
VA = 131 0.7˚
VB = 113 -123.4˚
VC = 113 124.7˚
IA = 200 -0.5˚
IB = 2478 172.3˚
IC = 2480 6.7˚
IG = 212 -11.3˚
EVENT SUMMARY 10002
BREAKER 1
BREAKER 2
BKR ALARM SUBMENU
BKR 1 ALARM COUNTER
ALARM COUNT
MECH. OP. TIME 0
ELEC. OP. TIME 0
BKR INACTIVITY 0
POLE SCATTER 0
POLE DISCREPANCY 0
MOTOR RUNTIME 0
CURRENT
INTERRUPTED 0
LAST RESET:
03/15/2001 00:01:00