U.5.28
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Front-Panel Operations
Front-Panel Automatic Messages
Front-Panel Automatic Messages
The SEL-421 Relay automatically displays alert messages. Any message
generated due to an alert condition takes precedence over the normal
ROTATING DISPLAY and the MAIN MENU. Alert conditions include these
significant events:
➤
Event reports and trips
➤
Status warnings
➤
Status failures
For event reports (including trip events) and status warnings, the relay
displays the full-screen automatic message that corresponds to this event, only
if the front-panel display is in the time-out or standby condition (the relay is
scrolling through the default display points/enabled metering screens of the
ROTATING DISPLAY or is displaying the MAIN MENU). When a status
warning or event is triggered, the relay full-screen presentation is similar to
the screens of
.
Figure 5.32
Sample Status Warning and Trip EVENT SUMMARY Screens.
If you are on site using the SEL-421 Relay front panel in menus and screens
other than the MAIN MENU and a status warning occurs or an event report
triggers, the relay shows automatic messages at the bottom of the active
screen in the message area. For example, the message area shows RELAY
STATUS WARNING for a status warning.
status warning notification that appears in the message area of a LOCAL
CONTROL (local bit) screen. If a trip event occurs while you are using a
front-panel screen, the message area notification reads RELAY EVENT.
When you repeatedly press
{ESC}
(as if returning to the MAIN MENU)
during this warning or trip alert situation, the relay displays the full-screen
automatic message concerning the warning or trip in place of the MAIN
MENU. If the front-panel display is at the MAIN MENU and a status warning
occurs, the full-screen warning replaces the MAIN MENU. After you view
the warning or trip screen, pressing
{ESC}
returns the LCD to the MAIN
MENU.
Figure 5.33
Sample Status Warning in the LCD Message Area.
03/15/01 GROUP 1
00:00:05.387
EVENT: BCG T
LOCATION: 48.47
FREQ: 60.00
SHOT: 1P=0 3P=1
BK1 OPEN
BK2 CLOSED
EVENT SUMMARY 10002
RELAY STATUS
SEL-421-R101-V0-
Z001001-D20010315
S/N=0001001234
RELAY ENABLED
TEMPERATURE WARNING
1 Closed (OK to TIE)
0 Open (No TIE)
BUS TIE INTERLOCK
1
0
RELAY STATUS WARNING