U.6.30
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Testing and Troubleshooting
Checking Relay Operation
Defeat the pole-open logic. Click the + button next to Breaker
Monitor to expand the Breaker Monitor branch of the Settings
tree view (see
). Click Breaker 1. You will see the
Breaker 1 dialog box similar to
. Enter
1
in the text
boxes for 52AA1 A-Phase N/O Contact Input–BK1, 52AB1
B-Phase N/O Contact Input–BK1, and 52AC1 C-Phase N/O
Contact Input–BK1. The text boxes in
appear if
Breaker Monitor setting BK1TYP := 1. If BK1TYP := 3, enter 1
in the 52AA1 N/O Contact Input–BK1 text box (the other
circuit breaker input boxes are dimmed.)
Figure 6.24
Breaker 1 Breaker Monitor Settings:
AC
SEL
ERATOR
Software.
Step 2. Set test values in the relay. Expand the Group 1 settings as
shown in
and select the Line Configuration button.
You will see the Line Configuration dialog box of
Confirm the default settings of Z1MAG at 7.80 and Z1ANG at
84.00. Click the + mark next to the Relay Configuration branch
to expand that Settings branch. Select the Directional button.
You will see the Directional dialog box similar to
. Confirm the following settings: 50FP is 0.60,
50RP is 0.40, Z2F is 3.90, Z2R is 4.00, a2 is 0.10, and k2 is 0.2.
The dialog box is dim since there are no settings to change. The
relay calculates these settings automatically because E32 is set
to AUTO. If you need to change these settings, set E32 to Y.
shows the calculations. See
Directional Element on page R.1.21 in the Reference Manual
for details on these relay calculations.
Figure 6.25
Group 1 Line Configuration Settings:
AC
SEL
ERATOR
Software.