TPS_ED1401-ENIT
12
Main Component
Operating Mechanism
Componenti Principali
Comandi di manovra
Various type of operating mechanism are avaiable for
switch-disconnector and Circuit Breaker TPS units:
Switch disconnector Operating Mechanism:
LT
Operator independent, operating mechanism which operates
under load. Operation energy is provided by a compressed spring
which, when released, causes the opening and closing of the
device after exceeding a deadlock.
3D
Operator independent, energy stored operating mechanism
which operates under load.
Operation in two steps:
1. Operation mechanism charging by lever or motor.
2. Stored energy released by opening/closing knob.
Disconnector Operating Mechanism
NL
Operator dependent manual operating mechanism which
operates under no-load. Opening and closing by lever.
DNL
Operator dependent manual operating mechanism which
operates under no-load. Opening and closing by lever (for
simultaneous double switching, in 2ICB unit)
Earthing Switch Operating Mechanism
E
Operator dependent manual operating mechanism which
operates under no-load. (only for earthing disconnector)
Circuit Breaker Operating Mechanism
TCB
The stored energy type operating mechanism with opening
and closing operations independent of the operator allows to carry
out a complete cycle O-C-O without spring charging; besides it
is suitable for the rapid (0-0,3s-CO–3min-CO) reclosing cycle.
Remote control of the circuit-breaker can be provided by means of
electrical accessories (e.g. spring charging motor, shunt opening
& closing release, undervoltage release in addition to auxiliary
contacts).
Negli Scomparti TPS sono disponibili vari tipi di comando
per sezionatori e Interruttori:
Per interruttori di manovra sezionatori:
LT
comando con manovra indipendente dall’operatore azionabile
sotto carico
3D
comando con manovra indipendente dall’operatore azionabile
sotto carico, ad accumulo di energia
Comando a due fasi:
1. Caricamento tramite la leva di manovra o motore.
2. Rilascio dell’energia accumulata tramite la manopola per
Apertura-Chiusura.
Per sezionatori:
NL
comando con manovra dipendente dall’operatore non
azionabile sotto carico
DNL
comando con manovra dipendente dall’operatore non
azionabile sotto carico (per doppio sezionamento simultaneo
(2ICB)
Per sezionatori linea a terra:
E
comando con manovra dipendente dall’operatore azionabile
in assenza di carico ( solo sezionatore di terra )
Per Interruttori:
TCB
Il comando meccanico ad accumulo di energia, con chiusura
ed apertura indipendenti dall’azione dell’operatore consente di
eseguire un ciclo O-C-O senza bisogno di ricaricare le molle;
inoltre garantisce la sequenza a ciclo rapido (O-0,3s-CO-3min-
CO) permettendo l’utilizzo come richiusore automatico.
Per il controllo a distanza dell’interruttore è prevista una serie
completa di accessori elettrici quali motore carica molle, bobina
di chiusura, sganciatore di apertura a lancio di corrente o per
minima tensione oltre ai contatti ausiliari di stato.
TCB Characteristics of electrical accessories / Caratteristiche accessori elettrici TCB
Electrical Auxiliaries
M.U. Spring charging motor Shunt Cl. release Shunt Op. Release
Undervoltage release
Auxiliary Contacts
Ausiliari Elettrici
U.M.
Motore
Bobina chiusura
Bobina Apertura
Sganciatore di minima tensione
Contatti Ausiliari
Ps
Pc
Ps
Pc
Charging Time
Tempo di Carica
S
15
Power Supply
Alimentazione
a.c.
V
24-48-110-220 ±10% (50Hz) ; 120-240 ±10% (60Hz)
d.c.
V
24-48-110 ±10%
(
For different Value Contact SEL
- Per valori differenti contattare SEL)
Power
Potenza
a.c.
VA
250
50
850
850
d.c.
W
250
50
450
450
150
15
Rated current
Corrente nominale
a.c. 250V
(cos ø 1)
A
15
a.c. 250V
(cos ø 0.6)
A
6
Switch-Disconnector Characteristics of electrical accessories / Caratteristiche accessori elettrici per Sezionatori
3D Operating Mechanism / Comando 3D
LT Operating Mechanism / Comando LT
Electrical Auxiliaries
M.U. Spring charging motor Shunt Cl. release Shunt Op. Release Auxiliary Contacts
Motor
Auxiliary Contacts
Ausiliari Elettrici
U.M.
Motore
Bobina chiusura
Bobina Apertura
Contatti Ausiliari
Motore
Contatti Ausiliari
Ps
Pc
Ps
Pc
Charging Time
Tempo di Carica
S
15
7
Power Supply
Alimentazione
a.c.
V
24-48-110-220 ±10% (50Hz) ; 120-240 ±10%
(60Hz)
d.c.
V
24-48-110 ±10%
Power
Potenza
a.c.
VA
250
50
850
850
800
150
d.c.
W
250
50
450 - 650
(*)
450 - 650
(*)
800
150
Rated current
Corrente
nominale
a.c. 250V
(cos ø 1)
A
15
15
a.c. 250V
(cos ø 0.6)
A
6
6
d.c. 125V
A
0,6
0,6
NOTE:
LT operating mechanism is also used in Vacuum circuit breaker units
ICBV and ILCBV. In ICBV unit it is installed in the normal position (with earthing
switch on the bottom part); in ICBV unit it is installed in the upside-down
position (with earthing switch on the top part). Motorized operating mechanism
is not provided for this application.
NOTE:
Il comando tipo LT viene utilizzato anche su scomparti con interruttore
in Vuoto ICBV ed ILCBV : nel primo scomparto viene installato in posizione
normale (con messa a terra nella parte inferiore), nel secondo viene installato
in posizione rovesciata (con messa a terra nella parte superiore). Per questa
applicazione non è prevista la motorizzazione del comando.
(*)
For Motorized 3D Operating Mechanism.
(*)
Per comando 3D Motorizzato.