13

TPS_ED1401-ENIT

Standards

Norme

IEC Standards

TPS is manufactured and tested in conformity with the latest 

issues of the following IEC standards.

IEC 62271-1

 Common specifications for high voltage switchgear 

and controlgear.

Ambient temperature:

Maximum value: 40°C 

Maximum value of  24 hours average: 35°C

Minimum value:  –5°C

Altitude of installation:

Up to 1000 m. 

Above 1000 m.  consult SEL S.p.A.

IEC 62271-200

 A.C. Metal enclosed switchgear and controlgear 

for rated voltage above 1kV and up to 52kV

Switchgear classification:

 PI class (metallic partitioning)

Loss of service continuity:

 LSC2A

Internal  arc  classification:

 class AFL to 12.5kA /1s (access 

restricted to authorized personnel only for front and lateral access)

on request: AFLR - 16KA / 1s

IEC 62271-103

 High voltage switches for rated voltage above 

1kV and up to 52kV

Class M1/E3

• 

1000 operating cycles close/open.

• 

100 make-break operating cycles at 100% mainly active load 

test duty 1 (rated current and 0.7 power factor).

IEC 62271-100

 High voltage alternating current circuit breakers

Standard circuit-breakers have class M1/E1.

Circuit-breaker class M1:

 circuit-breaker with normal mechanical 

endurance, type tested for 2000 mechanical operations.

Circuit-breaker class E1:

 circuit-breaker with basic electrical 

endurance not falling into class E2 (no extra tests are therefore 

required beyond the normal short-circuit type test).

On request class M1/E2 or class M2/E2 circuit-breakers are also 

available.

Circuit-breaker class M2:

 circuit-breaker with extended 

mechanical endurance, type tested for 10000 mechanical 

operations.

Circuit-breaker class E2:

 circuit-breaker with extended 

electrical  endurance  specifically  type  tested  operating  sequence 

(see tab.21 §6.112 of IEC 62271-100).

Rated operating sequence:

 O-t-CO-t’-CO

where:

• 

t=3 min for circuit-breaker not intended for rapid auto-

reclosing

• 

t=0,3 s for rapid auto-reclosing circuit-breakers

• 

t’=3 min

IEC 62271-102

 Alternating current disconnectors and earthing 

switches.

IEC 62271-105

 Alternating current switch - fuse combination.

IEC 60529

 Degrees of protection provided by enclosures (IP 

code).

Rispondenza normativa internazionale.

Il TPS è costruito  e collaudato in conformità con le emissioni più 

recenti dello standard  IEC di seguito elencate.

IEC 62271-1

 Prescrizioni comuni per l’apparecchiatura di 

comando e di manovra ad alta tensione.

Temperatura ambiente:

Valore massimo: 40°C

Valore massimo della media sulle 24 ore: 35°C

Valore minimo: -5°C

Altitudine di installazione:

Fino a 1000 metri

Oltre 1000 metri consultare SEL S.p.A. 

IEC 62271-200

 Apparecchiatura prefabbricata con involucro 

metallico per tensioni da 1kV a 52kV

Classificazione del quadro:

 Classe PI

Continuità di servizio:

 Classe LSC2A

Classificazione  per  tenuta  arco  interno:

 Classe AFL 12.5KA 

per 1s (Accesso di personale autorizzato al fronte ed ai lati del 

quadro) a richiesta: AFLR  -  16kA / 1s

IEC 62271-103

  Interruttori di manovra ed interruttori di 

manovra sezionatori per alta tensione

Classificazione: M1/E3

• 

1000 cicli di operazioni chiusura/apertura.

• 

100 cicli di operazioni stabilimento/interruzione al 100% della 

corrente di carico prevalentemente attivo come prescritto dal 

ciclo di prova 1 (corrente nominale e cosΦ 0.7).

IEC 62271-100

  Interruttori per alta tensione in corrente 

alternata. I nostri interruttori di fornitura standard sono classificati 

M1/E1.

Interruttore Classe M1:

 interruttore con durata meccanica 

normale (sottoposto a prove di tipo meccaniche per 2000 

manovre).

Interruttore Classe E1

: interruttore con durata elettrica di base 

che non rientra nella categoria E2 (non sono necessarie prove 

supplementari oltre la normale prova di cortocircuito). 

A richiesta, sono disponibili interruttori di classe M1/E2 oppure 

interruttori M2/E2.

Interruttore Classe M2:

 interruttore con durata meccanica 

estesa (sottoposto a prove di tipo meccaniche per 10000 

manovre).

Interruttore Classe E2:

 interruttore con durata elettrica estesa 

sottoposto  ad  una  specifica  sequenza  operativa  di  prova  (vedi 

tab.21 §6.112 della normativa IEC 62271-100). 

Sequenza di operazione nominale:

 O-t-CO-t’-CO

dove:

• 

t=3 min : per interruttori non previsti per la richiusura rapida

• 

t=0,3 s : per interruttori previsti per richiusura rapida

• 

t’=3 min

IEC 62271-102

 Sezionatori e sezionatori di terra a corrente 

alternata e a tensione superiore a 1000 V.

IEC 62271-105

 Interruttori di manovra-sezionatori combinati 

con fusibili ad alta tensione per corrente alternata.

IEC 60529

 Gradi di protezione (codice IP).

CEI-016 

Regola tecnica di riferimento per la connessione di 

utenti attivi e passivi alle reti AT e MT delle imprese distributrici 

di energia elettrica.

Summary of Contents for TPS 12kv

Page 1: ...1 TPS_ED1401 ITIN...

Page 2: ...TPS_ED1401 ENIT 2...

Page 3: ...B 2MCB 20 VTs and CTs units FIM FIM5 FIM7 FMM MTV MTVS MTA Scomparti con TA e TV FIM FIM5 FIM7 FMM MTV MTVS MTA 24 Cables and Busbars Earthing units CME ESM Scomparti per messa a terra di cavi e sbarr...

Page 4: ...e applicazioni su reti di distribuzione elettrica secondaria Power supply companies Power stations Cement industry Automotive industry Iron and steel works Windmills Solar plant Textile paper and food...

Page 5: ...lati in gas SF6 e dove impiegati interruttori isolati in vacuum Impiegati su reti di distribuzione elettrica in media tensione fino a 24kV per sezionamento protezione e misura Ampliabili in qualsiasi...

Page 6: ...tion with reduced maintenance under normal operating conditions High level of electrical endurance when breaking FLESSIBILITA Una vasta gamma di prodotti che coprono le necessit presenti e future Modu...

Page 7: ...To Failure MTTR MDT Mean Time To Repair Tutto il processo produttivo del TPS avviene seguendo lo specifico manuale del nostro sistema di qualit Il sistema di qualit stato riconosciuto da una organizz...

Page 8: ...hio ed elettrica elevate Assenza di manutenzione delle parti che eseguono il sezionamento Sicurezza e stabilit di funzionamento Dimensioni ridotte Switch disconnector The switch disconnector is made u...

Page 9: ...ora pi sicura l interfaccia operatore apparecchiatura il sezionatore dotato di due tipi di segnalazione di posizione 1 Un sinottico animato solidale ai contatti mobili dell apparecchio 2 Un obl fronta...

Page 10: ...polvere ed assicura la tenuta all impulso atmosferico sulla superficie esterna dell ampolla Vacuum technology Nowadays the interruption of current in vacuum is recognised as the dominant technology i...

Page 11: ...lto o in basso divenendo un polo interruttore passante Questa caratteristica consente di avere dimensioni del quadro estremamente ridotte e compatte e di accoppiarsi solidamente e facilmente con i pol...

Page 12: ...ura ed apertura indipendenti dall azione dell operatore consente di eseguire un ciclo O C O senza bisogno di ricaricare le molle inoltre garantisce la sequenza a ciclo rapido O 0 3s CO 3min CO permett...

Page 13: ...recenti dello standard IEC di seguito elencate IEC 62271 1 Prescrizioni comuni per l apparecchiatura di comando e di manovra ad alta tensione Temperatura ambiente Valore massimo 40 C Valore massimo d...

Page 14: ...or IEC 62271 103 100 Breaks at In p f 0 7 Class E3 Mechanical Operation Earthing Switch IEC 62271 102 1 000 Operations Class M1 Electrical Operation Earthing Switch IEC 62271 102 making capacity 5 Cla...

Page 15: ...kA 2 5 x IK Tempo di tenuta a corto circuito tK s 3 1 3 Grado di protezione sul fronte IP 3X Grado di protezione interno IP 20 Operazioni Meccaniche IMS IEC 62271 103 1 000 Manovre Classe M1 Operazio...

Page 16: ...iore circuiti ausiliari Manometer for TPS Switch Manometro per Sezionatore TPS Surge arresters Scaricatori Basic Equipment SM SM5 BSM SMS Equipaggiamento di base Switch and Earthing Switch with making...

Page 17: ...duct Canalina superiore circuiti ausiliari Surge arresters Scaricatori Voltage Indicator Spie presenza tensione Basic Equipment CM CM5 IOC BM Equipaggiamento di base Cables Holder Reggicavi Bottom pla...

Page 18: ...ra con potere di chiusura Voltage Indicator Spie presenza tensione Visibility of main contacts on switch disconnector Obl ispezione contatti principali su sezionatore Mechanical position indicator Ind...

Page 19: ...tore Auxiliary contacts on switch and earthing switch Contatti ausiliari su linea e su terra Keylocks and padlock holder Blocchi a chiave e Lucchettabilit Upper input output cables box Ingresso Uscita...

Page 20: ...ve su interruttore Aperto Optional Accessories ICB SCB Componenti Opzionali Motor for circuit breaker Motorizzazione interruttore Auxiliary contacts on switch and earthing switch Contatti ausiliari su...

Page 21: ...mponenti Opzionali Motor for circuit breaker Motorizzazione interruttore Auxiliary contacts on switch and earthing switch Contatti ausiliari su linea e su terra Keylocks and padlock holder Blocchi a c...

Page 22: ...or for circuit breaker Motorizzazione interruttore Auxiliary contacts on switch and earthing switch Contatti ausiliari su linea e su terra Keylocks and padlock holder Blocchi a chiave e Lucchettabilit...

Page 23: ...MCB Componenti Opzionali Motor for circuit breaker Motorizzazione interruttore Auxiliary contacts on switch and earthing switch Contatti ausiliari su linea e su terra Keylocks and padlock holder Blocc...

Page 24: ...bilit Upper input output cables box Ingresso Uscita cavi dall alto Base Zoccolo LV compartment for auxiliary circuits Cassonetto ausiliari BT Anti condensation heater Resistenza anticondensa Upper aux...

Page 25: ...ter Resistenza anticondensa Upper auxiliary circuits duct Canalina superiore circuiti ausiliari Fuses Fusibili Up to 3 VTs 2 VTs Phase to Phase or 3 VTs Phase to Earth Fino a 3 TV 2 TV Fase Fase o 3 T...

Page 26: ...al Accessories CME ESM Componenti Opzionali Auxiliary contacts on switch and earthing switch Contatti ausiliari su linea e su terra Keylocks and padlock holder Blocchi a chiave e Lucchettabilit Upper...

Page 27: ...ntatti ausiliari su linea e su terra Keylocks and padlock holder Blocchi a chiave e Lucchettabilit Upper input output cables box Ingresso Uscita cavi dall alto Base Zoccolo LV compartment for auxiliar...

Page 28: ...ntacts on earth switch Contatti ausiliari su sezionatore di terra N 3 Fuses 0 5A 24kV and fuses holder N 3 Fusibili 0 5A 24kV e portafusibili Cables terminal connection point Attacco cavi MBMP Meterin...

Page 29: ...Up to 3 CTs Fino a 3 TA Up to 3 VTs Fino a 3 TV N 3 Fuses 0 5A 24kV and fuses holder N 3 Fusibili 0 5A 24kV e portafusibili MBMC Metering unit with lower outgoing cables MCMP Metering unit with lower...

Page 30: ...i Standard Dati dimensionali L 375 L 500 SM SMS FIM FS BSM ESM SM5 FS5 L 500 L 750 FIM5 FSM SMM SMMR FIM7 L 750 ICB ICBR ICBLT SCB SCBR SCBLT 2ICB 2MCB L 500 L 750 CM5 CME MBER L 500 L 750 FMM MTA MBM...

Page 31: ...rno Dati dimensionali L 750 ICB ICBR ICBLT SCB SCBR SCBLT 2ICB 2MCB L 375 ICBV ILCBV L 375 L 500 SM SMS FIM FS BSM ESM SM5 FS5 L 500 L 750 CM5 CME FIM5 MBER FSM SMM SMMR FIM7 L 375 BM IOC CM MTV MTVS...

Page 32: ...no Dati dimensionali L 750 ICB ICBR ICBLT SCB SCBR SCBLT 2ICB 2MCB L 375 ICBV ILCBV L 375 L 500 SM SMS FIM FS BSM ESM SM5 FS5 L 500 L 750 CM5 CME FIM5 MBER FSM SMM SMMR FIM7 L 375 BM IOC CM MTV MTVS L...

Page 33: ...375 350 840 500 350 840 750 350 840 The use of base simplifies cable connection helps to keep the correct bending radius of the cables and reduces the trench depth in civil engineering works L utilizz...

Page 34: ...op or to the bottom of the units In the upwards exhaust version there are two possible solutions available Exhaust gases are canalized directly in the atmosphere see Fig 1 Exhaust gases are canalized...

Page 35: ...the units is used to direct the gases outside In this way the gases will loose their energy before going out through the grid doors La versione che espelle i gas combusti verso il basso utilizza il v...

Page 36: ...estrarla per impedire la chiusura della Terra E Keylock with earthing switch closed When the earthing switch is closed turn the key clockwise and remove it in order to prevent the opening of the eart...

Page 37: ...Comando LT Comando NL Comando E 3D Operating mechanism TCB Circuit Breaker unit operating mechanism Not for ILCBV For ILCBV TCB Circuit Breaker unit operating mechanism Comando 3D Comando TCB per scom...

Page 38: ...s Protection Relay Accessori Rel di protezione Protection relay installed in LV compartment Protection relay installed in LV Block compartment Esempio di rel montato in cassonetto BT Esempio di rel mo...

Page 39: ...pi complesso non lo permettono i rel ed i circuiti ausiliari saranno alloggiati in apposito cassonetto BT posizionato sopra o sul fronte del quadro The LV compartment can be installed on the roof or...

Page 40: ...5 Fig 6 Fig 7 Fig 8 Lateral Input Output Cables Ingresso Uscita cavi Laterale Fig 6 7 Lateral input cables from CM unit Fig 8 Lateral Outgoing cable system from ICBV ILCBV to transformer Fig 6 7 Soluz...

Page 41: ...ristiche elettriche Discharge rated current 10 kA Corrente nominale di scarica Rated voltage 3 33 kV Tensione nominale Discharge max current 100 kA Corrente massima di scarica Discharge current for 2...

Page 42: ...per protezione trasformatori Per la scelta dei fusibili necessario conoscere alcune importanti caratteristiche del trasformatore e confrontarle con quelle del fusibile Trasformatore Potenza nominale P...

Page 43: ...25 31 5 40 50 63 80 100 125 23 24 6 6 10 10 16 16 20 25 31 5 40 50 63 80 100 33 36 4 6 6 10 10 10 16 20 25 31 5 40 40 50 63 36 36 4 6 6 10 10 10 16 16 20 25 31 5 40 50 63 Standard fuses Fusibili stand...

Page 44: ...f powered protection relay Sganciatore di apertura a bassa energia fornito di serie con rel autoalimentati Spring charging motor optional Motore carica molle per interruttore opzionale Other Accessori...

Page 45: ...ng knob no 2 signalling lamps Two pole circuit breaker for auxiliary protection Withdrawable two pole fuse holder base for auxiliary protection Withdrawable three pole fuse holder base for secondary V...

Page 46: ...di servizio per esempio commutando automaticamente sulla linea di riserva alla mancanza delle rete elettrica principale Per il sistema ACO necessario un segnale di presenza tensione da ogni modulo di...

Page 47: ...s with LT operating mechanism Sistema di scambio automatico ACO tra due 2 IMS con comando LT Mechanical interlock between two switch disconnectors with LT operating mechanism Interblocco meccanico fra...

Page 48: ...ting degree 40 Grado Isolamento 40 mm Single core Unipolare 25 290 320 360 35 300 340 360 390 50 320 350 380 410 70 340 380 400 440 95 370 400 430 460 120 390 420 450 480 150 400 440 470 500 185 430 4...

Page 49: ...li scomparti al pavimento tramite tasselli ad espansione utilizzando la foratura indicata SM FS IOC CM SM FS IOC CM ICBV ILCBV ICBV ILCBV SM5 FS5 CM5 CME SM5 FS5 CM5 CME FSM SMM MBMC FSM SMM MBMC ICB...

Page 50: ...ximum 2 cables for phase 240 mm Massimo 2 cavi fase da 240 mm H6 470 Maximum 1 cable for phase 120 mm Massimo 1 cavi fase da 120 mm H7 470 Maximum 2 cables for phase 120 mm Massimo 2 cavi fase da 120...

Page 51: ...51 TPS_ED1401 ENIT Download our PDF Catalog Scarica il nostro Catalogo in PDF 10 04 14...

Page 52: ...TPS_ED1401 ITIN 52...