P8-25
Frequency switchover point
between acceleration time 1
and acceleration time 2
0.00Hz
〜
Maximum
frequency
Default
:
0.00Hz
P8-26
Frequency switchover point
between deceleration time 1
and deceleration time 2
0.00Hz
〜
Maximum
frequency
Default
:
0.00Hz
This function is effective when the acceleration/deceleration time is not
selected by switching the input terminal. It is used to select different
acceleration/deceleration time according to the operating frequency range
without passing through the input terminal during the running of the inverter.
Figure 6-20 Schematic diagram of the hopping frequency during acceleration and deceleration
Output frequency Hz
Time t
Jump frequency 1
Jump frequency 2
Jump frequency amplitude
Jump frequency amplitude
Figure 6-21 Schematic diagram of acceleration/deceleration time switching
Output frequency Hz
Set frequency
P8-25
P8-26
Acceleration time 2
Acceleration time 1
Deceleration time 1
Deceleration time 2
Time t
P8-27
Terminal JOG preferred
0
:
Invalid
1: Valid
Default
:
0
Figure 6-21 shows the switching of acceleration/deceleration time.
During the acceleration process, if the running frequency is less than P8-25,
the acceleration time 2 is selected; if the running frequency is greater than
P8-25, the acceleration time 1 is selected.
During deceleration, if the running frequency is greater than P8-26, the
deceleration time 1 is selected. If the running frequency is less than P8-26,
the deceleration time 2 is selected.
This parameter is used to set whether the terminal jog function has the
highest priority.
When the terminal jog priority is valid, if the terminal jog command
appears during operation, the inverter switches to the terminal jog operation
state.
P8-28
Frequency detection
value FDT2
0.00Hz
〜
Maximum
frequency
Default
:
0.00Hz
P8-29
Frequency detection
hysteresis value (FDT2)
0.0%
〜
100.0%
(
FDT2 level
)
Default
:
5.0%
This frequency detection function is identical to the function of FDT1.
Please refer to the description of function codes P8-19 and P8-20.
P8-30
Arbitrary arrival
frequency
detection value 1
0.00Hz
〜
Maximum
frequency
Default
:
50.00Hz
P8-31
Arbitrary arrival
frequency detection
width 1
0.0%
〜
100.0%
(
Maximum frequency
)
Default
:
0.0%
Arbitrary arrival
frequency detection
value 2
0.00Hz
〜
Maximum
frequency
Default
:
50.00Hz
Arbitrary arrival
frequency detection
width 2
0.0%
〜
100.0%
(
Maximum frequency
)
Default
:
0.0%
P8-32
P8-33
When the output frequency of the inverter is within the positive and
negative detection range of any arrival frequency detection value, the ON
signal is output. Figure 6-22 shows a schematic of this function.