CPU 72x
24.05.2019
page 28
1.7.2.3
Digital Outputs
The digital outputs of the CPU 72x have the following output switching:
Fig.20: Connection diagram digital outputs
Legend:
Digital Outputs CPU 72x
-T/LT
-TH/LTH
Output type
FET, plus-switching
Output display
LED orange, lights up with Signal = 1
Power supply (US)
Nominal value
24 Vdc
36 Vdc
Limits
16.8
…30.0 Vdc
25.2
…45.0 Vdc
Power supply display (US)
LED green
Output voltage
23
Vdc
35
Vdc
Output current
with Signal = 1 max.
0.5
A
Short circuit current Is typ.
5 A, switch off time = 1.5 ms
Switch on time after short circuit
5
s
Short circuit display
LED ret
Total loading
1)
2
A // 4
A
Minimum switching current
100
µA
Limitation of inductive switch off voltage
Suppressor diode
Output delay
for Signal 0
1
600
µs
for Signal 1
0
800
µs
Switching frequency
resistive load
100
Hz
inductive load
2
Hz
Signal level of outputs without load
for Signal 0
max. 2
Vdc
for Signal 1
16.8
…30.0 Vdc
25.2
…45.0 Vdc
Effect with overload
outputs are switched off
Galvanic separation
Output
logic
Yes, simple insulation, opto-coupler
Output
output
No
Test voltage
560 Vac, 800 Vdc to logic and earth
1)
2
A at CPU 723-T
— 4
A at CPU 725-LT/LTH / CPU 727-T/TH
LE D
O u tp u t
FET
US
0V