STATUS & ALARM INDICATORS - LED 5 (green) OFF 

When power is first applied LED 1 should flash. 

When LED 5 is OFF, this indicates the LED (1) – (4) is showing the inverters STATUS, as per written 
notation to the right of the LED’s. In this mode there are no adjustments to be made. 

LED 1 Flashing

 indicates the WM1200 is in Auto Start mode, this indicates that no power is being 

drawn from the inverter so it has gone to SLEEP to save power. If no power is used within 12 minutes, 
LED 1 will flash at a slower rate therefore saving more power. 

LED 1 Stays ON

, the inverter has been commanded to provide power to the load (e.g. a light switch 

has been turned on) so it has gone from SLEEP mode to ON. Once the load has been removed (e.g. the 
light switch is turned off) the inverter will wait 10 seconds and return to SLEEP mode. 

 

It is good practice to have your WM1200 in SLEEP mode as often as possible. When the 
WM1200 is in SLEEP mode it uses 0.055 amps from the battery, when the inverter is in the ON 
mode it uses at least 0.6 amps from the battery. 

The amount of power required to go from SLEEP to ON is adjustable and is described on below. 

LED 2, 

AC Overload should normally remain OFF. If the inverter shuts down due to too much AC 

load being drawn from it then LED 2 will come ON. The WM1200 will remain in this condition for 2 
minutes after the AC load has been decreased to a safe level. LED 2 will flash if the inverter shuts down 
due to “time to shutdown”, see page 11. 

 

If the inverter remains in this condition after two minutes, the main DC Power Switch should be 
turned OFF and then back ON. 

LED 3 

DC Volts Low / High

 should normally remain OFF. If the inverter shuts down because the 

battery volts are too high then this LED will come ON. It will remain ON until normal battery volts are 
restored. 

 

If the inverter shuts down due to not enough battery volts, then LED 3 will flash. 

 

LED 3 will continue to flash until the battery volts have risen sufficiently. In this case, charge the 
battery by starting the vehicle or using a battery charger. 

The low voltage point that the inverter will cut out is adjustable to suit your particular battery. 

LED 4, 

Temperature Overload

 should normally remain OFF. If the inverter shuts down due to the 

heatsink getting too hot, then this LED will come ON. If the inverter shuts down due to the transformer 
getting too hot, then this LED will FLASH. The inverter will remain shut down until the temperature 
has lowered to a safe level; the inverter will then come back ON. 

 

If this LED is coming on regularly, either reduce the amount of load on the inverter or try to move 
the inverter to a cooler location. 

DEMAND START ADJUST - LED 5 (green) ON 

It is sometimes necessary to adjust the auto start sensitivity to overcome what is called “Phantom 
Loads”. A phantom load is a load that tricks the inverter into thinking it should be ON instead of in 
SLEEP mode. 

The wiring of a house or a portable stereo system in standby are good examples of a phantom load. 
These loads serve no purpose but can increase battery drain by bringing the inverter ON. Hold the 
Mode button down, (approximately 1 second), LED 5 will turn ON indicating you are ready to adjust 
this setting. The WM1200 will leave the factory with a setting of 

4 Watts

. Now press the Mode button 

until the desired value is sought. LED’s 1 – 4 will return to Status Indication after 10 seconds if a key is 
not pressed. 

 

Each press of the Mode Button will increment the Demand Start Level. The adjustment starts from 
the previously stored setting. 

Summary of Contents for WM1200-12V

Page 1: ...T FINDING 8 SYSTEM MAINTENANCE 9 WM1200 MAINTENANCE 9 BATTERY MAINTENANCE 9 WM1200 ELECTRICAL SPECIFICATIONS 10 RADIO FREQUENCY INTERFERENCE 11 USING A SELECTRONIC KEYPAD WITH THE WM1200 12 12 SERIAL PORT WIRING 12 KEYPAD WIRING 12 KEYPAD FRONT PANEL Display not shown for clarity 12 STATUS 13 READINGS Keypad Grey Keys 13 SETTINGS Keypad Light Blue Keys 14 OPTIONS Keypad Light Blue Keys 15 DIAGNOST...

Page 2: ... Inverter must be installed in a dry cool dust free environment Please leave at least 300mm clearance around the sides and top of the Inverter and approximately 200mm at the base as this will aid the natural cooling of the Inverter The air vents on the underside of the WM1200 also need to be kept clear of obstructions BASE 300mm 300mm Mode PROUDLY DESIGNED MADE IN AUSTRALIA Demand Start Adjust Low...

Page 3: ...r system if this is the case a motor start fuse equal to or slightly higher than the maximum continuous current of the inverter should be used If in any doubt see your supplier or installer BATTERIES High quality deep cycle batteries offer good performance and are available in a wide variety of sizes DO NOT USE ordinary car batteries or engine starting batteries If a battery is rated only in Cold ...

Page 4: ...er on the front panel is in the OFF position LEVER DOWN Now connect the battery cables RED BATTERY POSITIVE BLACK BATTERY NEGATIVE These connections should be tight If using nuts bolts and washers they should be stainless steel At this point re check the connections before proceeding any further WARNING IF THE WM1200 EMITS A VERY LOUD TONE THE BATTERY LEADS HAVE BEEN CONNECTED IN REVERSE POLARITY ...

Page 5: ...too small to be sensed in the STANDBY mode The only disadvantage is that when the appliances are off the WM1200 will be drawing more power than it would in STANDBY mode When you first apply power the WM1200 will be in STANDBY mode There will be a quiet pulsing sound The WM1200 is now ready for use Mode Demand Start Adjust Low Volts Adjust Alarms 4 Watts DC Volts Low High TEMP Overload 8 Watts STAT...

Page 6: ...s down because the battery volts are too high then this LED will come ON It will remain ON until normal battery volts are restored If the inverter shuts down due to not enough battery volts then LED 3 will flash LED 3 will continue to flash until the battery volts have risen sufficiently In this case charge the battery by starting the vehicle or using a battery charger The low voltage point that t...

Page 7: ...utton until the desired value is sought LED s 1 4 will return to Status Indication after 10 seconds if a key is not pressed Low Volts Cut out LED 1 LED 2 LED 3 LED 4 10 0 Volts ON 10 1 Volts Slow flash ON 10 2 Volts Medium flash ON 10 3 Volts Fast flash ON 10 4 Volts Fastest flash ON 10 5 Volts ON 10 6 Volts Slow flash ON 10 7 Volts Medium flash ON 10 8 Volts Fast flash ON 10 9 Volts Fastest flash...

Page 8: ...ould be potentially dangerous so we advise you to consult your system designer immediately 4 INVERTER SHUTS DOWN WITH LOW VOLTS If your WM1200 has shut down because of low DC volts it could be due to the following 1 A sustained large load could be causing the battery volts to drop below the cut out voltage a The Battery Bank is too small for the loads you wish to use consult your system designer b...

Page 9: ... of such high capacity it is essential that you wear protective clothing some form of eye protection and rubber soled work boots Please regard your batteries with a great deal of caution and if in any doubt entrust this work to your installer 1 Every week carry out a thorough visual inspection of all battery wiring taking particular note of the condition of inter connections between cells 2 Check ...

Page 10: ...ctory Setting Output Voltage 240V AC 4 Nominal DC Input No Load to Full Load Output Current 5 8A AC 15A AC Max Continuous Max Surge Output Wave Shape Output Frequency Total Harmonic Distortion Efficiency True Sine Wave 50Hz 0 01 4 Peak 91 Full load 85 Power Factor Limitations Nil Input Output Isolation 1 875VAC Memory Retention Permanent Operating Temperature Range 10 C to 50 C Conforms to standar...

Page 11: ...n your installation It is recommended that the power system including the inverter be housed at least 15 metres from the home Ensure an earth stake is placed as close to the inverter as possible and connected to the inverter via a short length of wire See the INSTALLATION section of this manual for wiring Avoid running DC cables into the home if at all possible If this cannot be avoided run DC and...

Page 12: ... 8 Brown RATINGS LABEL Serial Port 1 8 KEYPAD WIRING Serial Port looking at the base of the inverter 1 2 3 4 5 6 7 8 Keypad from rear 1 2 3 4 5 6 KEYPAD FRONT PANEL Display not shown for clarity NEXT DISPLAY UP DOWN SETTINGS OPTIONS DIAG NOSTICS CURRENT SHUNT 1 CURRENT SHUNT 2 CURRENT SHUNT 3 AC LOAD READINGS INPUT READINGS GENERATOR CONTROL INVERTER STATUS TIME BATTERY READINGS ALARM Remote Keypa...

Page 13: ...d start mode waiting for another load to turn on This feature is extremely important as it conserves valuable battery power when no appliances are on The amount of power or load that the Inverter needs to start up is adjustable see page 5 for details CONT mode CONTINUOUS means that the Inverter will be on at all times regardless of whether appliances are connected or not This situation is useful i...

Page 14: ...N Set Parameters DS SENSE DS Watts 12W Set Parameters Demand Start When in STANDBY mode the inverter will require a load of 4 watts or greater to turn on to full 240V power This setting can be adjusted between 4 to 16 watts In most cases the default setting of 4W would be suitable If there is a load which the WM1200 won t sense then increase this value until the WM1200 goes into demand start pulsi...

Page 15: ...various internal inverter values These are not able to be changed from the keypad Press NEXT key Diagnostics Press the NEXT key to access diagnostics screens Tx Temp 1 Diagnostics Indicates transformer temperature Note the reading is NOT in degrees Celsius HS Temp 53C Diagnostics Indicates Heatsink temperature Note the reading IS in degrees Celsius D S I 2 Diagnostics Indicates Demand Start curren...

Page 16: ...l purchase The provision of this warranty shall not apply if the unit has been subject to misuse neglect act of God accidental damage or has been used for a purpose for which it is not intended Unauthorised modification or repair will void your warranty To ensure a smooth and speedy response to your warranty claim please complete and return your reply paid warranty card within 30 days from date of...

Page 17: ... NSW 2171 NSW 2480 Australia Australia Ph 02 9606 0279 Ph 02 6689 1430 Fax 02 6689 1109 Reid Technology Ltd 3 5 Auburn Street Solar Inverter Services Takapuna 13 Thirteenth Ave North Shore City Sawtell Auckland NZ NSW Ph 9 489 8100 2452 Fax 9 489 8585 Ph 02 66581733 ps reidtechnology co nz SELECTRONIC AUSTRALIA 25 Holloway Drive Bayswater Victoria 3153 Australia Phone 03 9762 4822 Fax 03 9762 9646...

Reviews: