Large amounts of DC current can be drawn by your LD700-24,
care must be
taken.
Fixed Installation
All fixed installation battery connections must be securely bolted,
using stainless steel nuts and bolts. To protect the connection from
corrosion smear a small amount of Vaseline or similar over the
joint. Never place batteries directly onto a concrete floor, place
timber or similar material beneath the batteries.
LD700-24
Inverter
Battery Bank
*System Fuse
To Load
* A system fuse (of at least 35 Amps) should be placed before the battery.
An HRC motor start type is recommended. (See your system designer for
details).
Warning
As a matter of safety, Selectronic strongly recommend that all fixed
installations be designed and installed by appropriately qualified person. The Solar
Energy Industries Association in your state or territory can provide names of accredited
system designers and installers.
All AC wiring MUST be carried out by an accredited electrician and must conform to
AS3000 and/or any relevant local standards.
The output voltage from an inverter is as lethal as mains electricity.
Electrician‟s Note
All earth‟s AC and DC should be bonded
RFI/Lightning Earth stake should be within 3m of the inverter
The LD700-24 is suitable for connection to MEN wiring
Any AC changeover switch must be a „break before make‟ type