SP LINK | Configuration Settings
Doc #OI0005 Rev26 2020
|
41
Alternate AC Source Power
sets the capacity of the Alternative AC Source. If the
alternative AC Source is a generator then set this to its continuous power rating.
If the Alternative AC Source is shore power then set this to the rating of the shore
power outlet.
Min AC Voltage
and
Max AC Voltage
. These parameters are set as a percentage
of the Nominal AC Voltage setting (under the Inverter tab). If the AC Source voltage
goes outside these limits the SP PRO will immediately disconnect from the AC
Source.
Min AC Frequency
and
Max AC Frequency
. The parameters are set as a
percentage of the Nominal AC Frequency setting (under the Inverter tab). If the AC
Source frequency goes outside these limits the SP PRO will immediately disconnect
from the AC Source.
Extern. Contactor/CT
.
If a pass though current of greater than 63A AC (125A AC
SPLC1200 and SPLC1202) is required then this setting is enabled when an
external
contactor and current transformer
of up to 1000A AC is installed. The current rating
of the external current transformer is entered in
External CT
.
See separate Installation instructions TN0057 available from the web site under the
Support tab.
The
AC INPUT LOGGING
is a Quality of Service monitoring function which sets the
Peak Voltage
threshold at which the inverter will record a performance data event.
(Peak Voltage of AC rather than RMS - 240V AC has a peak voltage of 340 V)
If you have particularly sensitive loads such as computers and plasma TVs, you may
choose to set this to a low value to monitor power quality and record any unexpected
high voltages coming from external supply sources.
Alternative Source. Configuration settings are used in place of the Primary Source settings and the
AC Source Power setting (in Quick Start section). The SP PRO uses these settings when running a backup
generator in a Solar Hybrid system, a second generator in an Off Grid system or shore power in a mobile
installation.
The Alternative Source is selected when the configured digital input is active. The digital input is configured
using the Normal/Alternate Input Power Selector parameter in the Inputs/Outputs section.
If a backup generator is required in a Solar Hybrid (On Grid) system, the optional Grid Fail Generator Backup
Module will need to be installed.
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...