SP LINK | Configuration Settings
Doc #OI0005 Rev26 2020
|
45
Generator Auto Start
The use of an auto start generator in an Off Grid system is essential as a backup energy source in times of poor
Renewable Energy production. In an Solar Hybrid (ON Grid) system the installation of an auto start generator
can also provide excellent backup in times of extended outages without the need for oversized battery bank.
This section explains how to use the generator to maximise battery life whilst obtaining the lowest operating
costs on the system. The Generator Auto Start tab enables you to change the conditions under which the
generator will start and stop. When a generator is started it will give first priority to service the AC Loads and
any leftover available generator capacity will be used to charge the batteries.
GENERATOR LOCK OUT OVERRIDE
On Low Battery Voltage
: As a safety net the SP PRO
will always start the generator based on battery voltage,
regardless of the battery SoC or the status of the Generator
Lockout. When the battery voltage drops below the
On Low
Battery Voltage
settings, the generator will start and run for
the Minimum Run Time.
On Low SoC:
When the
On Low SoC
is enabled and the
state of charge falls below
Start SoC
at any time during the
GENERATOR LOCK OUT period the generator will start and
run until the SoC reaches
Stop SoC
or at the least for the
Generator Minimum Run time.
The ON SoC NORMAL setting applies at times other than when other SoC Start
Stop functions are active including during Generator Lock Out times. If SoC falls
below
Start SoC%
the generator will be started and will charge until
Stop SoC%
or for Generator Minimum Runtime if
Stop SoC%
is reached before the minimum
runtime has elapsed. By not allowing the generator to take the batteries to 100%
avoids the generator from being too lightly loaded as batteries become full. It is
more efficient to allow Renewable sources to fill the batteries to 100%
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...