SP LINK | Configuration Settings
58
|
Doc #OI0005 Rev26 2020
Multiple Phase
is a Legacy setting for backward compatibility to older multiphase
systems.
Balance 3 Phase AC Source
only works with a three phase or split-phase
Powerchain system and will attempt to balance the generator phases, regardless of
any imbalance in the load power. The two settings will attempt to balance the phases
within a percentage of the total generator capacity.
Powerchain Inverters Per Phase
. Set automatically after assigning the SP PROs in
the Powerchain Inverter Assignments tab. For example in a three phase system with 6
SP PROs there will be 2 Powerchain Inverters per phase.
Enable Multiple Chargers
will help balance the charge current across the phases in a
three phase or split-phase powerchain system.
Generic AC Coupling
is only suitable for Solar Hybrid (On-Grid) systems and allows
the grid connected solar to continue to supply power to the load and to charge the
battery bank during a grid outage.
This setting allows the SP PRO to “kick off” or back off the power of any grid tie
inverter that is connected to the AC Load side of the SP PRO by ramping the
frequency of the AC output of the SP PRO. This AC Frequency ramp is triggered
during a grid outage when the battery voltage or charge current rises above the
SP PRO’s active charge voltage or current target. When the battery voltage or charge
current drops below the battery charge target, the output frequency of the SP PRO will
ramp back down.
Enabled
- The frequency will ramp all the way to the Frequency Ramp Limit before
ramping down again to the nominal Frequency.
MicroGrid
- The frequency will start ramping down again as soon as the charge
current and voltage fall below the SP PRO charge targets. This setting can be used
when the AC coupled grid inverter is configured with a frequency/watt response,
providing smoother control of the AC coupled grid inverter output.
Frequency Ramp Limit
sets the maximum “Generic AC Coupling” ramp frequency
above the “Nominal AC frequency”. For example if the Nominal AC frequency is 50 Hz
and the Frequency Ramp Limit is set to 2.5, then the output frequency of the SP PRO
will ramp to 52.5 Hz during a Generic AC Coupled frequency ramp.
Frequency Ramp Rate
sets the rate of the “Generic AC Coupling” frequency ramp.
The SP PRO has the ability to automatically attempt to recover from a fault situation. If
System Fault Recovery
is enabled the SP PRO will monitor the situation that created
the fault, such as low battery voltage, and return the inverter to operation if the battery
voltage returns to a suitable level.
Similarly if
Unit Fault Recovery
is enabled an internal problem within the SP PRO,
such as overheating, is monitored and normal operation continued if the problem is
resolved.
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...