SP LINK | Performance Monitoring
74
|
Doc #OI0005 Rev26 2020
AC Coupled Low DC Recovery
This feature is only available in systems that have AC coupled solar installed. It uses the AC coupled solar to
recover from a Low DC voltage or Low SoC shutdown.
This feature is used when the AC Source (Generator or Grid supply) is not available, possibly due to a failed
generator or long term grid outage.
To use the
AC Coupled Low DC Recovery
feature follow these simple steps.
1. Wait until the sun is up and there is enough sunlight to charge the batteries.
2. Turn off all the loads connected to the SP PRO. If this is not done then the
AC Coupled Low DC Recovery
mode will exit within 5 seconds.
3. Long Press ON button Twice. The SP PRO will go into
AC Coupled Low DC Recovery
mode and come on
to power up the AC coupled grid inverters. The battery LEDs on the front of the SP PRO will flash red when in
this mode. If the AC coupled solar does not start charging the batteries within 10 minutes then the SP PRO will
exit this mode.
4. Wait until Low DC shutdown recovers. When the battery LEDs stop flashing red and the SP PRO remains on
then the system has recovered.
5. Turn on your loads. The battery has now recovered enough to run the loads. Minimise power usage to avoid
another shutdown.