16
Selectronic Australia
Rev 41 - Dec 2022
Installation
DC Wiring SPMC Models
Warning:
Copper wiring must be used throughout. Observe polarity of
all
battery wiring. Reverse
battery polarity will cause irreversible damage.
All SPMC models
do not
contain an internal fuse or DC breaker. The DC wiring must be fitted with appropriate
fusing or circuit breakers.
The fuse or circuit breaker must be located in a user-accessible position and be in close proximity to the
battery system. The battery system must be installed according to the applicable installation standards.
There are four DC wiring connections that should be made. B+ and B-, Battery Sense / pre-charge and
optional mid-point monitoring. The Battery Sense / pre-charge connections can be made with light duty cable
(1.0mm
2
or greater).
DC wiring should be fed through the appropriate gland and terminated into the correct terminals.
Connect the battery negative lead – with the insulation stripped back 28mm – to the SP PRO’s battery
negative screw terminal. Tighten the hex screw with the driver provided. Repeat the same process with the
positive battery lead. Ensure that
no
part of the wiring insulation is clamped in the SP PRO battery terminals.
DC terminal torque settings – SPMC and SPLC
SPMC main DC terminals
SPLC main DC terminals
SPMC & SPLC
Pre-charge terminals
8.0 to 10.0Nm
8 to 10Nm
1.5 to 1.8Nm
DC Wiring SPLC Models
Warning:
Copper wiring must be used throughout. Observe polarity of
all
battery wiring. Reverse
battery polarity will cause irreversible damage.
The SPLC1200 and SPLC1202 models
do not
contain an internal fuse or DC breaker. The DC wiring must be
fitted with appropriate fusing or circuit breakers. Any fuse or circuit breaker must be located in a user-
accessible position and be in close proximity to the battery system. The battery system is hazardous and must
not be accessible by the user.
DC wiring should be fed through the appropriate gland and terminated to the correct terminals.
Connect the battery negative lead – with the insulation stripped back 28mm – to the SP PROs B- screw
terminal. Repeat the same process to connect the positive battery lead to the B+ terminal.
The Battery Sense / pre-charge, B+ and B-, and optional mid-point connections can be made with light duty
cable (1.0mm
2
or greater) – cable
must
be double insulated. Connect the battery negative lead – with the
insulation stripped back 12mm – to the SP PROs pre-charge negative screw terminal. Repeat the same
process with the positive battery lead and optional mid-point lead.
MULTIPLE Hazardous Energy and Voltage Sources
DC wiring is fed from multiple sources including internal capacitors. Care must be taken to ensure
that under no circumstances can the user access or touch wiring even after the operation of external
circuit breakers or fuse assemblies.
SPMC1201 – SPLC1200 – SPLC1202 models operate from a hazardous DC voltage (120VDC). Care
must
be
taken to ensure users cannot come into contact with the DC supply.
Cabling and Fusing